Temp Measured By Sensor Connected To Cgm Zone Temp Input; Temp Measured By Sensor Connected To Cgm Ics Temp Input; Misc Input Status Submenu; Cgm Ice Build Command Input - Trane IntelliPak CGAF Series Programming, Troubleshooting Manual

Air-cooled cold generator, "h" and later design sequence, with 3-dtm scroll compressors
Table of Contents

Advertisement

Refrigerant Ckt 2 - Temperature Data
Suction 72.0 F
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
CGM Zone Temp Input
1. Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
CGM ICS Temp Input
1. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Re-enter STATUS
2. Pressing the NEXT key will display the beginning of
the Submenu.
3. Press the NEXT key again to advance to the following screen.

Misc Input Status Submenu

Press ENTER to View Data in This Submenu
1. Press the ENTER key until the following screen is displayed.
2. Press the NEXT key to bypass this menu and advance to
"GBAS 0-5VDC Module Status Submenu"

CGM Ice Build Command Input:

1. Press the NEXT key until the following screen is displayed.

CGM Evap Soln Flow Switch Input:

1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 1 - Pressure Data
Suction
72 PSIG
1. Press the NEXT key until the following screen is displayed.
Refrigerant Ckt 2 - Pressure Data
Suction
65 PSIG
1. Press the NEXT key until the following screen is displayed.
Compressor 1A Phase Currents - Amps
Phase A
86
Phase B
1. Press the NEXT key until the following screen is displayed.
Compressor 1B Phase Currents - Amps
Phase A
81
Phase C
Sat Liquid
97.0 F
75.0 F
62.0 F
OFF
FLOW
Liquid
265 PSIG
Liquid
251 PSIG
84
78
System Operating Status
Used on Units: 40-60 Ton with Superheat/Subcooling
Module installed
Possible Values: -40.0 to 200 F
Used on Units: All Units
Possible Values: -40.0 to 200 F
Used on Units: With TCI Module Installed
Possible Values: -40.0 to 200 F
Used on Units: With Ice Building Control Option
Possible Values: Off, Make Ice
Used on Units: All Units
Possible Values: Flow, No Flow
Used on Units: All Units with Superheat/Subcooling
Possible Values: Suction = 0.0 to 100.0 PSIG
Liquid = 0.0 to 400.0 PSIG
Comp Off
Used on Units: 40 - 60 Ton Units with Superheat/Cooling
Possible Values: Suction = 0.0 to 100.0 PSIG
Liquid = 0.0 to 400.0 PSIG
Comp Off
Used on Units: With Current Sensing Module
Possible Values: 0 to 255
Used on Units: With Current Sensing Module
Possible Values: 0 to 255
21