56
Control System
Components
1A15, 1A16, 1A17, Dual Analog
Input/output Module;
Analog Output: The Analog
Output is a voltage only signal.
2-10 Vdc at 22mA
J2: 14 - 26 AWG with a
maximum of two 14 AWG
J2-1 Output #1 to J2-3 (ground),
J2-4 Output #2 to J2-6 (ground).
CH530 provides a 2-10 Vdc
analog signals as Outputs. The
Output's maximum source
capability is 22mA. The
maximum recommended length
to run this signal is included in
the table below.
Maximum Length to Run external Output signals
Gauge
Ohms per Foot
14
0.00 2823
16
0.004489
18
0.007138
20
0.01135
22
0.01805
24
0.0287
26
0.04563
28
0.07255
Note: the above table is for copper conductors only.
Analog Input:
The analog input can be
software switched between a
voltage input or a current input.
When used as a current input a
200 Ohm load resistor is
switched in.
0-12 Vdc or 0-24 mA Analog Inputs
CH530 accepts either a 2-10 Vdc
or 4-20 analog input suitable for
customer external control. The
type is determined at unit
commissioning during feature
installation.
J2: 14-26 AWG with a maximum
of two 14 AWG
J2-2 Input #1 to
J2-3 (ground).
J2-5 Input #2 to
J2-6 (ground).
Power, 24 +/- 10 percent Vdc, 60
mA maximum, Trane IPC3
protocol.
Length (Feet)
Length (Meters)
1062.7
668.3
420.3
264.3
166.3
104.5
65.7
41.4
324
203.8
128.1
80.6
50.7
31.9
20
12.6
CVGF-SVU02B-E4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cvgf 400Cvgf 1000