Control System
Components
B) Refrigerant Differential Pressure
Indication Output:
A 2 to 10 Vdc analog output is
provided instead of the previous
condenser pressure output
signal. This 2 signal corresponds
to a predetermined minimum
and maximum pressure settings
setup at commissioning of this
feature. This relationship can be
altered using TechView
required.
The "Minimum Delta Pressure"
is typically set to 0 psi and will
then correspond to 2 Vdc. The
"Maximum Delta Pressure " is
typically set to 30 psi and
corresponds to 10 Vdc.
Figure 19. Delta pressure setting
10 vdc
2 vdc
Minimum Delta
Pressure Setting
The Minimum Delta Pressure
Calibration setting has a range of
0-400 psid (0-2758 kPa) in
increments of 1 psid (1kPa). The
Maximum Delta Pressure
Calibration setting has a range of
1-400 psid (7-2758 kPa) in
increments of 1 psid (1kPa). The
condenser refrigerant pressure is
based on the Condenser
if
Refrigerant Temperature sensor.
The evaporator refrigerant
pressure is based on the
Saturated Evaporator Refrigerant
Temperature Sensor.
Maximum Delta
Pressure Setting
CVGF-SVU02B-E4