Hex
Diagnostic Name and
Code
Source
1F1
Starter Fault Type III -
Compressor 1A
1F2
Starter Fault Type III -
Compressor 1B
1F3
Starter Fault Type III -
Compressor 2A
1F4
Starter Fault Type III -
Compressor 2B
5C7
Starter Module
Memory Error Type 1 -
Starter 2A
5C8
Starter Module
Memory Error Type 1 -
Starter 2B
Starter Module
5C5
Memory Error Type 1 -
Starter 1A
Starter Module
5C6
Memory Error Type 1 -
Starter 1B
Starter Module
5C9
Memory Error Type 2 -
Starter 1A
5CA
Starter Module
Memory Error Type 2 -
Starter 1B
RLC-SVU01B-E4
Diagnostics
Severity
Persistence
Immediate
Latch
Immediate
Latch
Immediate
Latch
Immediate
Latch
Info
Latch
Info
Latch
Info
Latch
Info
Latch
Immediate
Latch
Immediate
Latch
Criteria
As part of the normal start
sequence to apply power to the
compressor, the Shorting
Contactor (1K3) and then the
Main Contactor (1K1) were
energized. 1.6 seconds later
there were no currents
detected by the CT's for the last
1.2 Seconds on all 3 phases.
The test above applies to all
forms of starters except
Adaptive Frequency Drives.
Same as Starter Fault Type III -
Compressor 1A
Same as Starter Fault Type III -
Compressor 1A
Same as Starter Fault Type III -
Compressor 1A
Checksum on RAM copy of the
Starter LLID configuration
failed
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Same as Starter Module
Memory Error Type 1 -
Starter 2A
Reset
Level
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
55