Hex
Diagnostic Name and
Code
Source
5CF
Starter 2A Comm
Loss: MP
Starter 2A Dry Run
6A9
Test
5D0
Starter 2B Comm
Loss: MP
6AA
Starter 2B Dry Run
Test
Starter Contactor
CC
Interrupt Failure -
Compressor 2A
CA
Starter Contactor
Interrupt Failure -
Compressor 1A
CB
Starter Contactor
Interrupt Failure -
Compressor 1B
52
Diagnostics
Severity
Persistence
Immediate
Latch
Immediate
Latch
Immediate
Latch
Immediate
Latch
Special
NonLatch
Mode
Special
NonLatch
Mode
Special
NonLatch
Mode
Criteria
Starter has had a loss of
communication with the MP for
a 15 second period.
While in the Starter Dry Run
Mode either 50% Line Voltage
was sensed at the Potential
Transformers or 10% RLA
Current was sensed at the
Current Transformers.
Starter has had a loss of
communication with the MP for
a 15 second period.
While in the Starter Dry Run
Mode either 50% Line Voltage
was sensed at the Potential
Transformers or 10% RLA
Current was sensed at the
Current Transformers.
Detected compressor currents
greater than 10% RLA on any or
all phases when the
compressor was commanded
off. Detection time shall be 5
second minimum and 10
seconds maximum. On
detection and until the
controller is manually reset:
generate diagnostic, energize
the appropriate alarm relay,
continue to energize the
Evaporator Pump Output,
continue to command the
affected compressor off, fully
unload the effected compressor
and command a normal stop to
all other compressors. For as
long as current continues,
perform liquid level and fan
control on the circuit effected.
Same as Starter Contactor
Interrupt Failure - Compressor
2A
Same as Starter Contactor
Interrupt Failure - Compressor
2A
Reset
Level
Local
Local
Local
Local
Remote
Remote
Remote
RLC-SVU01B-E4