Trane Tracer CH.530 RLC-SVU01B-E4 Owner's Manual page 41

“ho” design sequence, easyview and dynaview interfaces
Table of Contents

Advertisement

Hex
Diagnostic Name and
Code
Source
87
External Chilled Water
Setpoint
89
Evaporator Entering
Water Temperature
Sensor
High Differential
1C6
Refrigerant Pressure -
Circuit 1
High Differential
1C7
Refrigerant Pressure -
Circuit 2
High Evaporator
584
Liquid Level - Circuit 1
5B7
High Evaporator
Liquid Level - Circuit 2
RLC-SVU01B-E4
Diagnostics
Severity
Persistence
Info
NonLatch
Info
NonLatch
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Criteria
a. Function Not "Enabled": no
diagnostics.
b. "Enabled": Out-Of-Range
Low or Hi or bad LLID, set
diagnostic, default CWS to next
level of priority (e.g. Front
Panel SetPoint). This Info
diagnostic will automatically
reset if the input returns to the
normal range.
Same as External Chilled Water
Setpoint
The system differential
pressure for the respective
circuit was above 19.2 bar for 2
consecutive samples or more
than 10 seconds.
Same as High Differential
Refrigerant Pressure - Circuit 1
The liquid level sensor is seen
to be at or near its high end of
range for 80 contiguous
minutes while the compressor
is running. (The diagnostic
timer will hold, but not clear
when the circuit is off). Design:
80% or more of bit count
corresponding to +21.2 mm or
more liquid level for 80
minutes)
Same as High Differential
Refrigerant Pressure - Circuit 1
Reset
Level
Remote
Remote
Remote
Remote
Remote
41