Trane Tracer CH.530 RLC-SVU01B-E4 Owner's Manual page 32

“ho” design sequence, easyview and dynaview interfaces
Table of Contents

Advertisement

Hex
Diagnostic Name and
Code
Source
5DF
Comm Loss: External
Circuit Lockout,
Circuit #1
Comm Loss: External
5E0
Circuit Lockout,
Circuit #2
Comm Loss: External
5EA
Current Limit
Setpoint
Comm Loss: Fan
680
Control Circuit #1,
Stage #1
681
Comm Loss: Fan
Control Circuit #1,
Stage #2
682
Comm Loss: Fan
Control Circuit #1,
Stage #3
Comm Loss: Fan
683
Control Circuit #1,
Stage #4
684
Comm Loss: Fan
Control Circuit #2,
Stage #1
685
Comm Loss: Fan
Control Circuit #2,
Stage #2
686
Comm Loss: Fan
Control Circuit #2,
Stage #3
32
Diagnostics
Severity
Persistence
Special
Latch
Mode
Special
Latch
Mode
Special
NonLatch
Mode
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Criteria
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. MP will nonvolatilely
hold the lockout state (enabled
or disabled) that was in effect
at the time of comm loss.
Same as Comm Loss: External
Circuit Lockout, Circuit #1
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. Chiller shall discontinue
use of the External Current
limit setpoint and revert to the
next higher priority for Current
Limit setpoint arbitration.
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
RLC-SVU01B-E4