Hex
Diagnostic Name and
Code
Source
6BC
Comm Loss:
Evaporator Rfgt Drain
Valve - Ckt 2
Comm Loss:
688
Evaporator Rfgt Liquid
Level, Circuit #1
689
Comm Loss:
Evaporator Rfgt Liquid
Level, Circuit #2
Comm Loss:
5F0
Evaporator Rfgt
Pressure, Circuit #1
5F1
Comm Loss:
Evaporator Rfgt
Pressure, Circuit #2
Comm Loss:
5F8
Evaporator Water
Pump Control
5DD
Comm Loss: External
Auto/Stop
5E9
Comm Loss: External
Chilled Water Setpoint
RLC-SVU01B-E4
Diagnostics
Severity
Persistence
Normal
Latch
Immediate
Latch
Immediate
Latch
Immediate
Latch
Immediate
Latch
Normal
Latch
Normal
Latch
Special
NonLatch
Mode
Criteria
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. Note: This diagnostic is
replaced by diagnostic 5FB
below with Rev 15.0.
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. Note: This diagnostic is
replaced by diagnostic 5FB
below with Rev 15.0.
Same as Comm Loss: Chilled
Water Flow Switch
Same as Comm Loss: Chilled
Water Flow Switch
Continual loss of
communication between the
MP and the Functional ID has
occurred for a 30 second
period. Chiller shall discontinue
use of the External Chilled
Water Setpoint source and
revert to the next higher
priority for setpoint arbitration.
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote