Hex
Diagnostic Name and
Code
Source
MP: Reset Has
D9
Occurred
Oil Flow Fault -
1E1
Compressor 1A
Oil Flow Fault -
1E2
Compressor 1b
5A0
Oil Flow Fault -
Compressor 2A
5A1
Oil Flow Fault -
Compressor 2b
1E6
Oil Temperature
Sensor - Cprsr 1B
Oil Temperature
1E8
Sensor - Cprsr 2B
Oil Temperature
1E5
Sensor - Cprsr 1A
Oil Temperature
1E7
Sensor - Cprsr 2A
A1
Outdoor Air
Temperature Sensor
48
Diagnostics
Severity
Persistence
Info
NonLatch
Immediate
Latch
Immediate
Latch
Immediate
Latch
Immediate
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Criteria
The main processor has
successfully come out of a
reset and built its application. A
reset may have been due to a
power up, installing new
software or configuration. This
diagnostic is immediately and
automatically cleared and thus
can only be seen in the Historic
Diagnostic List in TechView.
The Intermediate Oil Pressure
Transducer for this compressor
is reading a pressure either
above its respective circuit's
Condenser Pressure by 1.05 bar
or more, or below its
respective Suction Pressure 0.7
bar or more for 30 seconds
continuously.
Same as Oil Flow Fault -
Compressor 1A
Same as Oil Flow Fault -
Compressor 1A
Same as Oil Flow Fault -
Compressor 1A
Bad Sensor or LLID
Bad Sensor or LLID
Bad Sensor or LLID
Bad Sensor or LLID
Bad Sensor or LLID. Note that if
this diagnostic occurs,
operational pumpdown will be
performed regardless of the
last valid temperature.
Reset
Level
Remote
Local
Local
Local
Local
Remote
Remote
Remote
Remote
Remote
RLC-SVU01B-E4