Fire Extinguishing System - Viessmann KOB Pyrot KRT Series Technical Data Manual

Krt 150 to krt 540 series wood-fired boiler
Table of Contents

Advertisement

Pyrot Technical Data

Fire Extinguishing System

The fire extinguishing system functions independent from
the electrical power and is flooding the material which is
still remaining in the in-feed auger in case of a back-burn.
The activation temperature is approx. 200° F (95° C).
Fire extinguishing system for the in-feed auger
Note: The fire extinguishing system for the in-feed auger
is part of the boiler.
- Line from the extinguishing water container to the b in.
valve (as short as possible).
- Valve thermostatic, Danfoss AVTA 15 122° F-194° F
(50°- 90°C) position 3 equals approximately
176° F (80° C).
- The lines must be executed as hard piping in metal (b in.).
- It must not be possible to shut off the cold water inlet
without the aid of tools.
- Be especially sure to comply with the instruction in
the Fire Protection section.
Legend
A Combustion
B Metering Container
C Fuel supply
D Extinguishing water container 6.6 USG (25 L)
E N1 Floater switch
CW Cold water supply b in. min. 30 psi (2.0 bar),
max. 45 psi (3.0 bar)
Fire extinguishing system for the conveyor auger
Note: The fire extinguishing system for the conveyor
auger is optional.
Fire Extinguishing System for the Down Pipe
Note: The fire extinguishing system for the down pipe
is optional.
Note: A slide valve is required as standard for an
unpressurized material store or a rotary valve
for a material storage with overpressure or
underpressure (charging with blower, e.g. wood
processing operations).
- The lines must be executed as hard piping in metal (b in.).
- It must not be possible to shut off the cold water inlet
without the aid of tools.
- Be especially sure to comply with the instruction in
the Fire Protection section.