Connecting A Plastic Flue Pipe (Pps) To A Moisture-Resistant Chimney (Mr Chimney Negative Pressure) - Viessmann VITOPLEX 200 Type SX2A Technical Manual

Oil/gas boilers 90 to 2000 kw
Table of Contents

Advertisement

Design information
(cont.)
c
Boiler flue connection 200/200
A Test port
B Optional connection for a flue gas high limit safety cut-out
Connecting a plastic flue pipe (PPs) to a moisture-resistant chimney (MR chimney, negative pressure)
A Plug-in adaptor by Schiedel
B Plewa adaptor
C Flue gas
D Secondary ventilation
E MR chimney
F Inspection aperture
Vitoradial 300-T condensing boilers may be connected to a moisture-
resistant chimney, if the chimney manufacturer can provide a calcula-
ted verification to DIN EN 13384.
OIL/GAS BOILERS
Boiler flue
Dimension [mm]
connection
7 mm
a
200/150
200
200/200
200
1
Boiler flue connection
2
Flue pipe
2 m long
1 m long
0.5 m long
3
Inspection piece, straight
or inspection bend 4
4
Inspection bend, 87°
or inspection piece, straight 3
A flue pipe that is pressure sealed and moisture-resistant in accord-
ance with Building Regulations should be used as connecting piece.
Plewa or Schiedel (quoting reference "Schiedel Steck-Adapter") sup-
ply this adaptor from the flue pipe to the MR chimney upon request.
b
c
d
150
270
184
270
227
VIESMANN
43
10