BOILER ACCESSORIES

Condensate pump
The condensate pump is required for low level
boiler installation where the condensate for
removal has to be pumped upwards.
The condensate pump is also equipped with
an alarm switch (potential free contact) which
Technical data
Supply voltage
Power consumption P1
Current draw
Protention class
Acid resitance
Pump
Electronically commutated spherical motor with permanent magnet rotor/impeller
Max. pump head
Max. flow rate
Noise level (Lw)
Max. system temperature
Min. ambient temperature
Safety contact
Tank volume
Package dimensions
Package weight
Part no.
can be used to switch off the condensing
boiler/ASHP to prevent the condensate
tank from overflowing. Separate alarm LED
indicators are also fitted to the pump.
Relay open when triggered, capacity 250 VA
0.7I (usable volume 0.5I)
215 x 215 x 180 mm
100 - 240 Volt
25 Watt
0.2 - 0.1 A
IP 44/Class F
pH2 or higher
54 kPa
460 I/h
46 (dB(a))
+60°C
non-freezing
1.6 kg
7374796