Information regarding design and operation
Note
2
Up to 15 m
collector area can be linked up in series to form a single array.
Vitosol 200-T (flat roof, horizontal)
Connection from the left (preferred option)
A
A Collector temperature sensor in the flow line
Connection to the right
A
A Collector temperature sensor in the flow line
Vitosol 200-T (pitched roof, flat roof, elevated)
Single-sided connection from below (preferred version)
1 collector array
A
With this connection, the "relay kick" function on the Vitosolic 200 must
be enabled (see chapter "Functions" in the "Solar control units" sec-
tion).
A Collector temperature sensor in the flow line
With this installation, the following minimum flow rates in the (partial)
collector array must be ensured:
4 m
2
35 l/(h·m
2
)
5 m
2
30 l/(h·m
2
)
VITOSOL
(cont.)
15 m²
A Collector temperature sensor in the flow line
≥6 m
3 m
2 m
2 or more collector arrays (≥ 4 m
With this connection, the "relay kick" function on the Vitosolic 200 must
be enabled (see chapter "Functions" in the "Solar control units" sec-
tion).
A Collector temperature sensor in the flow line
15 m²
2
2
25 l/(h·m
)
2
2
45 l/(h·m
)
2
65 l/(h·m
2
)
2
)
A
A
12
VIESMANN
123