Honeywell AirAlert 96d Instruction And Installation Manual page 20

Multi-channel gas monitoring system
Table of Contents

Advertisement

7
Configuration
Tests (Sequential Test Mode)
Test Sequence
This simple test sequence enables the user to
activate each output and validate the operation of
each controller key and all display pixels, as well as
the different communication protocols.
Start Sim. Sequ. & Stop Sim. Sequ.
(Stop Simulation)
8. Tests
Test Sequence
Start Sim Sequence
Maximum load
See Simulation Mode section for more details.
The simulation mode allows for the simulation of gas
concentration over associated scale range on all
sensors. The simulated gas concentration values are
local to the controller.
Start with Tx00X (simulation starts with
sensor 00X)
Confirm (simulation activation)
Manning AirAlert-96d Gas Monitor
continued
19073 AIRALERT96D 05/2006 Prelim REVC Copyright © 2006 Honeywell Analytics. All Rights Reserved.
Maximum Load (Activation of All Controller
Components)
Oprt Mode (Controller Operating Mode)
8. Tests
Oprt Mode: normal
See System Operation section for more details.
1
Normal (normal controller operating mode)
2
Single Tx (activation of interrogation mode for a
single sensor)
3
Debug (activation of service mode to allow for
calibration without affecting events)
20

Advertisement

Table of Contents
loading

Table of Contents