Pointer Configuration

If a point is capable of becoming a pointer, the
Pointer Configuration icon
that point value; click this icon to open the Pointer
Configuration pop-up window:
Figure 4-27 - Pointer Configuration
The Pointer Configuration window allows you to
define a point within the same control system to
which the current point being configured will get or
send its property.
To set up a pointer, select a value from each of the
drop-downs:
• Area Controller - the area controller to which the
point will associate (should be the same control sys-
tem of the current point)
• Application Type - the name of the application type
• Application - the specific application to which the
point will connect
• Point - name of the input or output you want the cur-
rent point to send or get its value from. Connect an
input point to an output point of the same data type,
and vice versa (e.g., digital outputs to digital inputs,
analog inputs to analog outputs). An input point can-
not be associated to another input point, likewise, an
output point cannot be hooked to another output
point.
Example 1: A time schedule that has a digital output
that is turned on and off based on time is hooked to a digital
input of another application to perform a bypass action
based on the time of day.
Example 2: An analog combiner with four temperature
inputs can average the inputs and have the average as the
output value. The output is connected to the input of anoth-
er application to control off of the average temperature.
Click OK to save the settings; pointer information
will display in the Value field of the Edit Application
page. Click Cancel to exit.
Unit
appears to the right of
Each output point that has the ability to be a point-
er can point to multiple other input points within a
controller. To connect an output point to multiple in-
put points, click the Pointer Configuration icon of an
output. A pop-up window will open and display all
the input points connected to that output. (The page
will be blank if no point is connected currently.) Click
to highlight an input point and click Edit to modify,
or click Delete to disassociate the point and remove
from the list. To connect more points, click the Add
button; the Pointer Configuration pop-up window
opens.
Figure 4-28 - Pointer Configuration Window
Click OK to apply the setup and enable the point-
er. Click Cancel to exit without saving.

Log Configuration

Set up log parameters of an application instance by
clicking the Log Configuration icon
only for points that have logs). There are two possible
types of log configuration: analog and digital. Infor-
mation related to the point will appear when the point
is clicked. Click OK to save, or Cancel to exit.
NOTE: Grayed out icons appear when there is
no log configuration or alarm configuration
set up yet. Click on the grayed out icons to set
up a log configuration or advisory configura-
tion for the first time.