Key Features
Adjustable Setpoints
Capacity
•
Range = 50-100%
•
Preset at 100% for 6000-1,3,4
Preset at 50% for 6000-2
Low Drain Threshold
•
Range = 50-100%
•
Preset at 90%
Cycle Time
•
Range = 60-300 seconds
•
Preset at 60 seconds
Faults
Overcurrent
•
138% of Rated Current
•
System Shutdown
Fill System
•
Fill valve open for 6 hours without achieving capacity setpoint or cylinder full
•
System Shutdown
End of Cylinder Life
•
6 hours of operation while on cylinder full without achieving capacity setpoint
•
System Shutdown (See Pg. 14 for Manual Override)
*If the conductivity of your supply water is less than 100 micromho, consult Herrmidifier for specific circuit board
**Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.
Conductivity*
Micromhos
(approx.)
100
135
170
250
500
750
1000
adjustments and replacement tank information (GT-176-1).
Unit performance may be affected.
Operation on water of less than 60 micromho is not recommended.
Average Life**
Expectancy – Hrs.
(approx.)
2000
1900
1800
1300
800
650
500
5