SECTION V TROUBLESHOOTING GUIDE

All
Herrmidifier
6000
manufactured under strict quality control and are
subjected to a complete operational test. All circuit board
adjustments are made at the factory and should not be
adjusted
beyond
the
troubleshooting guide without first consulting a factory
representative. The following information is for your help
and reference. If you still experience difficulty after trying
these remedies, contact your Herrmidifier representative.
WARNING!
The Herrmidifier 6000 Series Electronic Steam
Humidifier cabinet was designed to house and
shield
the
components
interference. Absolutely NO other components
may be mounted inside or be electrically tapped
into the humidifier without Herrmidifier's express
written permission. Failure to heed this warning
will void your warranty.
TEST POINTS
Each circuit board (See Figure 12) features three test
points to aid in the troubleshooting process.
these test points works on a 0-4 VDC scale. "0 VDC" =
0%. "4 VDC" = 100%. All readings are between the test
point and ground (Molex J1, terminal 11 [far right of
molex connector, hours wire #11]).
Test Point #1:
Provides exact reading of drain threshold setting.
Test Point #2:
Provides circuit board reference voltage. Should always
read 4 VDC +/-2%.
Test Point #3:
Provides actual percentage of output. For example, a
unit running at 80% of maximum output would have a
Test Point #3 to ground reading of 3.2 VDC.
Series
Humidifiers
guidelines
set
in
from
outside
Each of
Maximum Capacity Setpoint
are
The potentiometer labeled "R39" located in the top left-
hand corner of the board allows adjustment of the unit's
this
All blower units have their capacity set from the
factory at 4 lbs/hr. These units can have their
capacity increased by increasing the capacity
adjustment potentiometer. Ensure there is
sufficient air circulation in the conditioned space
to prevent condensation on walls or ceiling
when increasing capacity beyond 4 lbs/hr.
capacity in the range of 50-100% of maximum.
Models
All
All
All
All
NOTE
Figure 12
Circuit Board Settings
Time Cycle
Low Drain
R23
Setting,
R18
Standard Settings
60 sec
90
High Conductivity Settings
(over 1000 micromhos)
84 sec
93
Softened Water Settings
(750-1000 micromho)
60 sec
92
Low Conductivity Settings
(<100 micromho)
60 sec
85
Capacity,
R39
100%
90%
95%
100%
13