I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

Key Features

Adjustable Setpoints:
Capacity
• Range = 50-100%
• Preset at 100% for 6000-1,3,4
• Preset at 50% for 6000-2
Low Drain Threshold
• Range = 50-100%
• Preset at 90%
Cycle Time
• Range = 30-180 seconds
• Preset at 60 seconds
ADJUSTABLE LOUVER
(6000-1, -2 UNIT)
INTEGRAL, QUIET
OPERATING FAN
(6000-1, -2 UNIT)
"CYLINDER FULL" ELECTRODE
(RED WIRE)
CYLINDER - REPLACEABLE
GLASS FILLED POLYPROPYLENE
DRAIN SYSTEM
(SEALED DRAIN VALVE, ADJUSTABLE
DRAIN THRESHOLD AND CYCLE
TIME PROVIDE EXTENDED LIFE.)
H e r r t r o n i c
M o d e l 6 0 0 0
®
Faults:
Overcurrent
• 138% of Rated Current
• System Shutdown
Fill System
• Fill valve open for 6 hours without achieving capac-
• System Shutdown
End of Cylinder Life
• 6 hours of operation while on cylinder full without
• System Shutdown
HERRMIDIFIER
ity setpoint or cylinder full
achieving capacity setpoint.
Operation using water of less than 100 micromho
is not recommended.
Typically 500-2000 hours of cylinder operation can
be obtained. Your actual cylinder life may be higher
or lower depending on the exact composition of
your water supply.
FILL SYSTEM
(INTEGRAL 1" AIR GAP PREVENTS
REVERSE SIPHONING TO POTABLE
WATER SUPPLY; "ADJUSTABLE
METERING VALVE ACCOMODATES
WATER PRESSURES UP TO 100 PSI."
INTERNAL CIRCUIT BREAKER
INTEGRAL HUMIDISTAT
(6000-1, -2 UNIT)
ISOLATED CONTROL COMPARTMENT
WITH SOLID STATE CONTROLS
POWER, CYLINDER FULL,
AND SERVICE INDICATOR LIGHTS
ON/OFF/DRAIN SWITCH
COVER INTERLOCK SWITCH
(PREVENTS UNIT OPERATION
WITH COVER OFF)
CONCEALED FILL AND
DRAIN CONNECTIONS
w w w. h e r r m i d i f i e r - h v a c . c o m