6000 series electronic steam humidifiers (24 pages)
Summary of Contents for Herrmidifier Herrtronic AD
Page 1
Please read these instructions carefully for trouble free operation and to get the most out of your purchase. For further information concerning this product, contact your local Herrmidifier representative. Herrtronic AD Series Installation, Operation and Service Manual...
Check List ..…………………………………………………………………………………………………………………………..12 Maintenance…………………………………………………………………………………………………………………………..13 SECTION V TROUBLESHOOTING GUIDE Trouble Shooting Unit Detected Faults…………..………………………………………………………………………………14 Trouble Shooting Non-Fault Activated Problems……..……………………………………………………………………15-16 Circuit Board Diagram …………………………………………………………………………………………………………..….17 Exploded View and Part Lists.…… …… ………………………………………….…………………………………………18-22 Unit Wiring Diagram……………… .……..………………………………………………………………………………………...23 Herrtronic AD Series Installation, Operation and Service Manual...
Trion, Inc. with an explanation of the problem. However, in the continuing operation of this humidifier, replacements of this part are your responsibility as part of routine maintenance. Herrtronic AD Series Installation, Operation and Service Manual...
Accordingly, the rate of boiling increases. Eventually, the Controlled humidification requires a very precise control system. The Herrtronic AD utilizes a solid state control to rate of boiling reduces the output capacity below the monitor performance and maintain humidity. Further, the "low drain threshold"...
Preset; setting varies by unit End of Cylinder Life Cycle Time • 45 Minutes of operation without achieving capacity setpoint • Range=60-300 Sec. • System Shutdown • Preset; setting varies by unit Herrtronic AD Series Installation, Operation and Service Manual...
Further, a high limit humidistat (located ten Engineering and Application feet downsteam of the humidifier steam distributor) Herrtronic AD Series Steam Humidifiers can be applied should be included for better system control. in a variety of applications. The simplest application consists of an "AD"...
The cabinet is designed to safely contain the working stated in these instructions. Do not place parts of the Herrtronic AD Series and dissipate heat to objects near the cabinet. Do not attach to dry protect the electronics. Herrtronic AD Series electronic wall without studs.
8% pitch back to the Herrtronic AD unit. Since steam output losses are directly related to the distance from the humidifier to the steam distributor, it is recommended: WARNING! Do not mount the standard steam distribution pipe in a NOTE vertical downflow duct.
Page 9
Herrtronic AD Series Installation, Operation and Service Manual...
A cable tie is provided to distributor must be ordered when installing in a vertical secure all control wiring. All control wiring should be 18 downflow duct. AWG or larger. Herrtronic AD Series Installation, Operation and Service Manual...
(See page 13 for proper connection procedure). Restart the humidifier following the above instructions. Herrtronic AD Series Installation, Operation and Service Manual...
Herrtronic AD Humidifier Checklist NOTE The Herrtronic AD Humidifier checklist is provided to help the installer insure a successful installation. If further assistance is needed from the Herrmidifier representative or the factory, the checklist is expected to be completed. If a jobsite visit is required from the Herrmidifier representative or the factory, and the checklist has not been accurately completed, additional charges will be required by the individual(s) representing Herrmidifier.
Always drain cylinder completely if unit will be off for an Switch. extended period of time. This will preserve the life of the 2. Turn off power to the unit. Disconnect electrode cylinder. power wires and cylinder full electrode wire from tank. Herrtronic AD Series Installation, Operation and Service Manual...
NOTE: The three fault conditions outlined above will cause the humidifier to shut down and the service light on the front of the unit to illuminate. To clear these faults, the main power must be turned “off” and back “on” again. Herrtronic AD Series Installation, Operation and Service Manual...
Check external shutoff valves and open if closed. cylinder. Check that fill solenoid coil is receiving 24 VAC. If yes, replace the solenoid. Check for break in wiring Replace the circuit board Herrtronic AD Series Installation, Operation and Service Manual...
Page 16
Check location and setting of high limit humidistat Cabinet leaks Check for loose connections Fill tube out of fill tee Steam cylinder out of drain cup Cabinet drain backing up, kink in drain line Herrtronic AD Series Installation, Operation and Service Manual...
Steam Cylinder Assemblies: EST-1002-4-1 Single Phase, 5 62#/hr. EST-1002-6-1 Three Phase, 5 62#/hr. EST-1002-6-2 Three Phase, 60-125#/hr. Parts List Item No. Description Steam Cylinder Assemblies: EST-416-2 Single Phase, 5-15#/hr. EST-416-3 Three Phase, 5-30#/hr. Herrtronic AD Series Installation, Operation and Service Manual...
Page 19
Herrtronic AD Series Installation, Operation and Service Manual...
Page 20
Herrtronic AD Series Installation, Operation and Service Manual...
Page 21
Herrtronic AD Series Installation, Operation and Service Manual...
Page 22
Herrtronic AD Series Installation, Operation and Service Manual...