E. Combustible Mantel
Refer to shaded areas of Figure 11.9 for the location and dimensions of a combustible mantel.
A combustible mantel may be positioned no lower than 12 in. (305 mm) above the top of the fireplace opening.
A combustible mantel may have a maximum depth of 12 in. (305 mm).
Combustible trim and materials cannot be placed within 6 in. (152mm) of the fireplace opening (top or sides).
Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of
the fireplace opening.
Combustible trim must not cover the metal surfaces of the fireplace.
Mantel clearance is in accordance with Section 7-3.3.3 of ANSI/NFPA211.
Figure 11.9 Clearances to Mantels or other Combustibles above Fireplace
42
Combustible Wall
2 x 4 stud wall
Standoffs
Seal joint with
non-combustible
sealant
1 1/2 in./38 mm
maximum
Non-combustible
Decorative Facing
such as:
Steel, iron, brick,
tile, concrete, slate,
glass, plasters.
Heatilator • EL36/EL42 • 4044-132 • Rev AD • 7/12
Combustible
Decorative Facing
12 in./305 mm
12 in./305 mm
minimum
6 in./152 mm
minimum
Measured from top of fireplace opening
7 ft (2134 mm)