Honeywell Tradeline T7300F series 2000 Installation Instructions Manual page 5

Commercial microelectronic conventional or heat pump thermostat
Table of Contents

Advertisement

T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Installer Setup
Number
(Press
Unoccupied
Temp Key to
Select
change)
Deadband.
30
Interstage
31
control point
(Q7300C,D
only).
Minimum on-
32
time.
Minimum off-
33
time for the
compressor.
Temperature
34
range stops in
heating.
Temperature
35
range stops in
cooling.
Not used.
36
a
Number 2 must be set to 1 to extend fan operation.
Number 22 must be set to 1 and remote sensor(s) must be installed.
b
Table 2. Thermostat Installer Setup Options (Continued)
Factory Setting
Display
Description
2
Heating and cooling
setpoints can be set no
closer than 2°F
(1.1°C).
0
Disabled.
2
2-minute minimum on-
time for heating and
cooling.
4
4-minute minimum off-
time for the
compressor.
90
Highest setpoint for
heating.
45
Lowest setpoint for
cooling.
Other Choices
(Press
or
Display
3 thru
Heating and cooling
10
setpoints can be set no
closer than the chosen
value:
3—3°F (1.7°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
1 thru
Temperature has to change
12
more than the chosen
value before the system
calls for the next stage.
(Example: 68°F (20°C) is
the heat setpoint, 2°F
(1.1°C) is the interstage
setting, temperature is
65.5°F (18.5°C), the
second stage turns on,
brings the temperature to
66°F (19°C) and turns off.
The heat pump continues
to run until the setpoint is
met.)
0 or 1
No minimum on-time or
1-minute minimum on-time
for heating and cooling.
0, 1, 2,
Minimum number of
3 or 5
minutes (0 thru 5) the
compressor will be off
between calls for the
compressor.
40 to 89 Temperature range (1°F
[0.6°C] increments) for
heating setpoint.
46 to 99 Temperature range (1°F
[0.6°C] increments) for
cooling setpoint.
5
key to change)
Description
Setting
62-0125—3