T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Installer Setup
Number
(Press
Unoccupied
Temp Key to
Select
change)
Deadband.
30
Interstage
31
control point
(Q7300C,D
only).
Minimum on-
32
time.
Minimum off-
33
time for the
compressor.
Temperature
34
range stops in
heating.
Temperature
35
range stops in
cooling.
Not used.
36
a
Number 2 must be set to 1 to extend fan operation.
Number 22 must be set to 1 and remote sensor(s) must be installed.
b
Table 2. Thermostat Installer Setup Options (Continued)
Factory Setting
Display
Description
2
Heating and cooling
setpoints can be set no
closer than 2°F
(1.1°C).
0
Disabled.
2
2-minute minimum on-
time for heating and
cooling.
4
4-minute minimum off-
time for the
compressor.
90
Highest setpoint for
heating.
45
Lowest setpoint for
cooling.
—
—
Other Choices
(Press
or
Display
3 thru
Heating and cooling
10
setpoints can be set no
closer than the chosen
value:
3—3°F (1.7°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
1 thru
Temperature has to change
12
more than the chosen
value before the system
calls for the next stage.
(Example: 68°F (20°C) is
the heat setpoint, 2°F
(1.1°C) is the interstage
setting, temperature is
65.5°F (18.5°C), the
second stage turns on,
brings the temperature to
66°F (19°C) and turns off.
The heat pump continues
to run until the setpoint is
met.)
0 or 1
No minimum on-time or
1-minute minimum on-time
for heating and cooling.
0, 1, 2,
Minimum number of
3 or 5
minutes (0 thru 5) the
compressor will be off
between calls for the
compressor.
40 to 89 Temperature range (1°F
[0.6°C] increments) for
heating setpoint.
46 to 99 Temperature range (1°F
[0.6°C] increments) for
cooling setpoint.
—
—
5
key to change)
Description
Setting
—
62-0125—3
Actual