Honeywell Tradeline T7300F series 2000 Installation Instructions Manual page 4

Commercial microelectronic conventional or heat pump thermostat
Table of Contents

Advertisement

T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Installer Setup
Number
(Press
Unoccupied
Temp Key to
Select
change)
System setting
12
adjustment
(models with
System key).
Not used.
13
Degree
14
temperature
display.
Displaying
15
temperature.
Clock format.
16
Intelligent
17
Fan™
operation.
Auxiliary
18
Contact
Operation.
Extended fan
19
operation in
heating
.
a
Extended fan
20
operation in
cooling.
Fan key adjust-
21
ment (models
with Fan key).
Remote
22
sensing.
Temperature
23
averaging
network
.
b
Not used.
24
Keypad lockout
25
level (keypad
lockout is
enabled and
disabled by dip
switch 1 on
back of
thermostat).
Duration of
26
temporary
override.
Not used.
27 thru 29
a
Number 2 must be set to 1 to extend fan operation.
Number 22 must be set to 1 and remote sensor(s) must be installed.
b
62-0125—3
Table 2. Thermostat Installer Setup Options (Continued)
Factory Setting
Display
Description
Depends
System selection.
on
model.
0
Temperature is
displayed in °F.
0
Temperature is
displayed.
0
12-hour clock format.
2
Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.
0
0 Time-of-day
contacts.
0
No extended fan
operation after the call
for heat ends.
0
No extended fan
operation after the call
for cool ends.
0
Fan setting key is
operational.
0
Remote sensing not
activated.
0
Temperature averaging
disabled.
0
No lockout.
3
3—Three hour
override.
Other Choices
(Press
or
Display
0, 1 or 2 0—System setting key is
operational.
1—Auto setting is disabled.
2—Auto only setting.
1
Temperature is displayed
in °C.
1
Temperature is not
displayed.
1
24-hour clock format.
0 or 1
0—Fan only operates with
calls for heating or cooling
in Occupied and
Unoccupied modes.
1—Fan operates
continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.
1
1—Economizer contacts.
1
Fan operation is extended
90 seconds after the call for
heat ends.
1
Fan operation is extended
90 seconds after the call for
cool ends.
1
Fan setting key is Auto
only.
1
Remote sensing activated.
1
Temperature averaging
between local sensor and
remote sensor(s) activated.
1 or 2
1—Lockout all keys on
thermostat except system
and fan settings, temporary
setpoint, clock and day
adjustments.
2—Lockout all keys except
set Current Day/Time,
increase
keys.
3 Lockout all keys except
temporary occupied, Set
Current Day/Time (for
clock, day adjustments).
1, 8 or
1—One hour override.
12
8—Eight hour override.
12—Twelve hour override.
4
key to change)
Description
Setting
and decrease
Actual

Advertisement

Table of Contents
loading

Table of Contents