Installer Setup; Set Temperature - Honeywell Tradeline T7300F series 2000 Installation Instructions Manual

Commercial microelectronic conventional or heat pump thermostat
Table of Contents

Advertisement

T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
ENTER OCCUPIED
PROGRAM MODE
RETURNS TO
NORMAL
OPERATIONS
SET OVERRIDE
Temporary
TEMPERATURE
OFFSET AND
ACTIVATE
Continuous
TEMPORARY
Unoccupied
OVERRIDE
ENTER HOLD MODE
Set System and Fan (select models)
The system default setting is Heat. The fan default is set
so the fan operates continuously in Occupied and
Recovery mode and with the heating or cooling
equipment in Unoccupied mode. Use the System and
Fan keys to change the settings.
The system settings are:
Em Heat (Q7300C,D and H heat pump models):
Emergency heat relay is on continuously. Thermo-
stat cycles highest stage of heat. Cooling system is
off. Compressor is de-energized.
Heat: Thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: Thermostat controls the cooling.
Auto: Thermostat automatically changes between
heating and cooling operation depending on the
indoor temperature.
The fan settings are:
On: Fan operates continuously.
Auto: Equipment controls the fan in the Unoccupied
mode. The Intelligent Fan™ operation (Installer
Setup number 17) offers three choices for the fan
operation in Occupied mode:
—fan turns on only when there is a call for heating
or cooling,
—fan operates continuously in Occupied mode,
—fan is on continuously in Occupied and recovery
modes.

Set Temperature

Refer to Table 1 for the default temperature setpoints.
See Owners Guide form number 63-4356 for complete
instructions on changing the setpoints.
62-0125—3
ENTER UNOCCUPIED
PROGRAM MODE
SET CURRENT DAY OR
PROGRAM DAY
Mon
Occupied
System
Heat
Set Program
Run
Occupied
Unoccupied
Program
Start Time
Start Time
Set Current
Clear
Occupied
Day/Time
Start Time
SET CURRENT
DAY AND TIME
CLEAR PROGRAM PERIOD
Fig. 2. Thermostat key locations and descriptions.
SET OCCUPIED
TEMPERATURE
SETPOINTS
AM
Room
Fan
Auto
Set Temperature
Occupied
Unoccupied
Day
Temp
Temp
Heat/Cool
Copy
Settings
System
Fan
SELECT
SYSTEM
OPERATION
COPY ONE
PROGRAMMED DAY
TO ANOTHER DAY
Table 1. Default Temperature Setpoints.
Control
Heating
70°F (21°C)
Cooling
78°F (25.5°C)

INSTALLER SETUP

NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the
factory-settings in Table 2 and if no changes are
necessary, go to the Installer System Test sec-
tion.
The Installer Setup is used by the installer to customize
the thermostat to specific systems. Installer Setup
numbers are listed in Table 2. The table includes all the
configuration options available.
A combination of key presses are required to use the
Installer Setup feature.
— To enter the Installer Setup, press and hold the Heat/
Cool Settings key with both the increase
decrease keys until the first number is displayed. All
display segments appear for approximately three
seconds before the number is displayed. See Fig. 3
and 4.
Set Program
Set Program
Start Time
Em Ht
Em Ht
Aux Ht
Aux Ht
Comm
Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System
Em Heat
Off
Fig. 3. LCD display of all segments.
2
SET UNOCCUPIED TEMPERATURE
SETPOINTS AND SCROLLS
THROUGH INSTALLER SETUP
AND SYSTEM TEST
INCREASE
TEMPERATURE
Change
OR TIME SETTING
Time/Temp
SELECT FAN
CHANGE BETWEEN HEATING
OPERATION
AND COOLING SETPOINTS
AND SCROLLS BACKWARDS
THROUGH INSTALLER SETUP
NUMBERS AND SYSTEM TEST
Occupied
Unoccupied
55°F (13°C)
90°F (32°C)
Set Day/Time
Set Day/Time
Temporary Setting Enrg
AM
PM
Heat
Cool
In
Recovery
Auto
Lo
Med
Hi
Wait
DECREASE
TEMPERATURE
OR TIME SETTING
M10233A
and
Sav
Room
%Humid
Remote
Only
Duct
Fan
On
Auto
M4916