T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT

INSTALLER SYSTEM TEST

Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
Table 3. Installer System Tests.
Test
Number
System Test Description
10 to 19
Heating equipment can be turned on and off.
20 to 29
Emergency heat (Q7300C,D,H [heat pump
models only]) equipment can be turned on
and off.
30 to 39
Cooling equipment can be turned on and off.
40 to 49
Fan equipment can be turned on and off.
60 0 to
Keyboard keys test.
60 19
70 to 79
Thermostat information including date code,
software versions and subbase identification
are displayed.
To start the system test:
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor
is cycled too quickly.
The minimum off time for compressors is
bypassed during the Installer System Test.
Press and hold the increase
the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Fig. 5 and 6.
Key to Press
Heating Equipment System Test
Heat/Cool Settings
Emergency Heating Equipment System Test (Q7300C,D,H [heat pump models only]).
Heat/Cool Settings
and
decrease keys, at
Table 4. Installer System Test Options
Test
Number
10
Enter heating equipment system test.
11
Stage-one heat turns on. The system fan is also energized.
12
Stage-two heat turns on. Stage-one heat and system fan remain on.
13
Stage-three heat turns on. Stage-one and stage-two heat with the system fan
are on.
12
Stage-three heat turns off.
11
Stage-two heat turns off.
10
Stage-one heat and system fan turn off.
20
Change from heating to emergency heating equipment system test.
21
Emergency heat and system fan turn on.
22
Highest stage heat turns on.
21
Highest stage heat turns off.
20
Emergency heat turns off.
Set Program
Set Program
Start Time
Em Ht
Em Ht
Aux Ht
Aux Ht
Comm
Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System
Off
Em Heat
Fig. 5. LCD Display of all segments.
TEST NUMBER
Fig. 6. Test number display.
NOTE: If a duct temperature sensor is installed, the
duct temperature is also displayed.
Refer to Table and Thermostat Information section for
directions and results of the specific system tests.
NOTE: Press Run Program to exit the system test. The
system test times out after four minutes without
any key presses.
Description
7
Set Day/Time
Set Day/Time
Temporary Setting Enrg
AM
PM
Heat
Cool
In
Recovery
Auto
Only
Lo
Fan
Med
Hi
Wait
Sav
Room
%Humid
Remote
Duct
On
Auto
M4916
M10257A
62-0125—3

Advertisement

Table of Contents
loading

Table of Contents