Important Safety Instructions
Electrical Recommendations: 120 V and
240 V Treadmills
Note: This is a recommendation only. NEC (National Electric
Code) guidelines or local region electric codes must be
followed.
You should have received a power cable that meets your local
electrical code requirements along with the equipment.
Precor treadmills must be connected to a 20 amp individual
branch circuit that can be shared only with one PVS. If you
need additional help with the power connections contact your
Precor authorized dealer.
Important
and neutral conductor to a receptacle. The conductors must not be
looped, "daisy-chained", or connected to any other conductors.
The circuit must be grounded according to NEC guidelines or local
region electric codes.
Figure 1: North American 120-volt, 20-amp power receptacle
Figure 2: North American 240-volt, 20-amp power receptacle
:
An individual branch circuit provides a hot conductor