%" approved
aluminum
or copper
tubing
is acceptable
for lengths
under 20 ft (6.1 m) if
local codes and gas supplier
permit.
•
If you are using Natural
gas, do not use copper
tubing.
•
lengths
over 20 fl (6.1 m) should
use larger tubing
and a different
size adapter fitting.
•
If your dryer has been converted
to use [.P gas, %" IP compatible
copper
tubing
can be
used. If the total length of the supply
line is more than 20 ft (6.1 m), use larger pipe.
NOTE:
Pipe-joint
compounds
that resist the action of I.P gas must be used. Do not use
TEFI.ON _'*tape.
•
Must include
a shutoff
valve:
An individual
shutoff
valve must be installed
within
6 feet
(1.8 m) of the dryer in accordance
with
the National
Fuel Gas Code, ANSI Z223.1.
The
location
should
be easy to reach for opening
and closing.
A
C
E
B
D
A. f_" fl_'xibl_" gas connector
B. .F_"pipe
to flare' adapte'r
fitting
C. _"
NP7 minimum
plugged
tapping
D. _//' NPT gas supply
line
E. Gas shutoff
valve
Gas supply
connection
requirements
•
Use an elbow
and a 3/8" flare x 3/8" NPT adapter fitting
between
the flexible
gas connector
and the dryer gas pipe, as needed
to avoid kinking.
•
Use only pipe-joint
compound.
Do not use TEFI.ON'*
tape.
•
This dryer must be connected
to the gas supply
line with
a listed flexible
gas connector
that complies
with the standard
for connectors
for gas appliances,
ANSI Z21.24.
Burner
input
requirements
Elevations
above 10,000
ft (3,048
m):
•
When
installed
above 10,000
ft (3,048
m) a 4% reduction
of the burner
Btu rating shown
on the model/serial
number
plate is required
for each
,000 ft (305 m) increase
in
elevation.
Gas supply
pressure
testing
•
[he dryer must be disconnected
from the gas supply
piping
system during
pressure testing
at pressures greater than _/2psi.
Dryer Gas Pipe
•
The gas pipe that comes out through the rear of your dryer has a %" male pipe thread.
6w'
B
(15.88 cm)
........
A. 1/_ ,, NPT gas supply
line
B. _"
NPT dryer pipe
k_J
Fire Hazard
Use a heavy
metal
vent.
Do not use
a plastic
vent.
Do not use a metal
foil vent.
Failure
to follow
these
instructions
can result
in death
or fire.
WARNING:
lo reduce the risk of fire, this dryer MUSI
BE EXHAUSTED
OUTDOORS.
IMPORTANT:
Observe
all governing
codes and ordinances.
[he dryer exhaust
must not be connected
into any gas vent, chimney,
wall, ceiling
or a
concealed
space of a building.