Nordyne 14 SEER User's Information And Installation Instructions Manual page 10

14 seer r-410a high efficiency split system outdoor air conditioner
Table of Contents

Advertisement

Green LED is not on,
module does not power up
Green LED intermittent,
module powers up only
when compressor
runs
TRIP LED is on but system
and compressor check OK
Determine
if both R and C module terminals are
connected. Verify voltage is present at module's R and
C terminals. Review 24VAC Power W iring (page 4) for
R and C wiring.
Determine if R and Y terminals are wired in reverse.
Verify module's R and C terminals
have a constant
source. Review 24VAC Power W iring (page 4) for R
and C wiring.
Verify Y terminal is connected to 24VAC at contactor
coil. Verify voltage at contactor coil falls below 0.5VAC
when off.
TRIP LED and ALERT LED
flashing together
ALERT Flash Code 3
(Compressor
Short Cycling)
displayed incorrectly
ALERT Flash Code 5, 6 or 7
(Open Circuit, Open Start Circuit
or Open Run Circuit) displayed
incorrectly
ALERT Flash Code 6 (Open
Start Circuit) displayed for Code 7
(Open Run Circuit) or vice versa
ALERT Flash Code 8
(Welded Contactor)
displayed incorrectly
Verify R and C terminals are supplied with 19-28VAC.
Verify Y terminal is connected to 24VAC at contactor
coil.
Verify voltage at contactor coil falls below 0.5VAC when
off.
Check that compressor
run and start wires are through
module's current sensing holes. Verify Y terminal is
connected to 24VAC at contactor coil. Verify voltage at
contactor coil falls below 0.5VAC when off.
Check that compressor run and start wires are routed
through the correct module sensing holes.
Determine if module's Y terminal is connected. Verify Y
terminal is connected to 24VAC at contactor coil. Verify
24VAC is present across Y and C when thermostat demand
signal is present.
If not, R and C are reverse wired. V erify
voltage at contactor coil falls below 0.5VAC when off.
Table 2. Module Wiring Troubleshooting
Adjustment
of Refrigerant
Charge:
CAUTION'.
Split system air conditioner equipment
contains liquid and gaseous refrigerant
under
pressure.
Adjustment
of
refrigerant
charge
should
only
be
attempted
by
qualified,
trained
personnel thoroughly
familiar with the
equipment.
Under no circumstances
should
the
homeowner
attempt
to
install and/or service
this equipment.
Failure to comply
with this warning
could
result
in equipment
damage,
personal injury, or death.
NOTE:
The
following
Refrigerant
Charging
Charts are applicable
to matched
assemblies
of our equipment
and at listed airflows for the
indoor coil. These units are matched with TXV
equipped indoor coils. Assemblies of indoor coils
and outdoor units not listed are not recommended
and deviations from rated airflows or non-listed
equipment combinations
may require modifica-
tions to the expansion device(s) and refrigerant
charging
procedures
for proper and efficient
system operation.
Refrigerant
Charging
Chart
--
Refer
to
Refrigerant Charging Charts for correct system
charging.
Optional Equipment
-- A functional checkout
should
be performed
in accordance
with the
checkout procedures
supplied with the
equipment.
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents