Trou Bleshooti Ng Tables - Nordyne 16 SEER User's Manual & Installation Instructions

16 seer two stage r-410a split system
Hide thumbs Also See for 16 SEER:
Table of Contents

Advertisement

TROUBLESHOOTING
- CONTINUED
Status LED
Status LED
Description
Status LED Troub[eshooting information
Short Cycling
= Thermostat demand signal is intermittent
Yellow "ALERT"
Compressor is
, Low line voltage (contact utility if voltage at disconnect is low)
Flash Code 3
running only
= Excessive liquid refrigerant in compressor
briefly
= Compressor bead ngs are seized
= Run capacitor has failed
= Low line voltage (contact utitlity if voltage at disconnect is
Yellow "ALE RT"
low)
Locked Rotor
= Check wiring connections
Flash Code 4
= Excessive liquid refrigerant in compressor
= Compressor bearings are seized
= Measure compressor oil level
= Outdoor unit power disconnect is open
= Compressor circuit breaker or fuse(s) is open
= Compressor contactor has failed open
--
Check compressor contactor wiring and connectors
--
Check for compressor contactor failure (burned, pitted
or open)
--
Check wiring and connectors
between supply and
Yellow "ALE RT"
Flash Code 5
Open Circuit
compressor
--
Check for low pilot voltage at compressor contactor coil
--
High pressure switch is open and requires manual reset
= Open circuit in compressor supply wiring or connections
= Unusually long compressor protector reset time due to extreme
ambient temperature
= Compressor windings are damaged
--
Check compressor motor winding resistance
= Run capacitor has failed
Open Start
= Open circuit in compressor start wiring or connections
YeIIow"ALERT"
Circuit
--
Check wiring and connectors between supply and the
Flash Code 6
Current only in
compressor S terminal
run circuit
, Compressor start winding is damaged
--
Check compressor motor winding resistance
, Open circuit in compressor run wiring or connections
YeIIow"ALERT"
Open run circuit
--
Check wiring and connectors between supply and the
Current only in
compressor R terminal
Flash Code 7
start circuit
= Compressor run winding is damaged
--
Check compressor motor winding resistance
Welded
YeIIow"ALERT"
Contactor
= Compressor contactor has failed closed
Flash Code 8
Compressor
= Thermostat demand signal not connected to module
always runs
YeIIow"ALERT"
LowVo[tage
= Control circuit transformer is overloaded
Control circuit
= Low line voltage (contact utility if voltage at disconnect is low)
Flash Code 9
< 17VAC
= Check wiring connections
* Flash code number corresponds to a number of LED flashes, followed by a pause and then
repeated. Trip and alert LED's flashing at same time means control circuit voltage is too low for
operation.
Table 4. LED Diagnostics