Kenmore 229.960330 Owner's Manual page 13

Continuous pilot/electronic intermittent ignition gas-fired cast iron steam boiler
Table of Contents

Advertisement

NATURAL GAS
Pipe Capactty- BTU Per Hourlnput
Length of
Includes Fittings
Pipe - Ft.
½"
¾"
1"
1%"
20
92,000
190,000
350,000
625,000
40
63,000
130,000
245,000
445,000
60
50,000
! 05,000
195,000
365,000
MANUAL
SHUT-OFF
VALVE
AUTOMATIC
VALVE
GROUND
JOINT
MANIFOLD
UNION
S OI.ENTTRAP
p l
FLOOR
LINE
_u
ELECTRIC
POWER
SUPPLY
All electrical work must conform to local codes, as well as
the National Electrical Code, ANSI/NFPA-70, latest revision.
Run a separate 120 volt circuit from a separate overcurrent
protective device in your electrical service entrance panel.
This should be a 15 ampere circuit. Locate a shut-off switch
at the boiler. It must be turned off during any maintenance.
Connect 120 volt electrical supply to the primary leads on
the 24 volt transformer. Solder and tape or securely fasten
these connections with wire nuts.
The boiler, when installed, must be electrically grounded in
accordance
with the requirements
of the authority having
jurisdiction or, in the absence of such requirements, with the
National Electrical Code, ANSI/NFPA No. 70-latest revision.
Run a 14 gauge or heavier copper wire from the boiler to
a grounded connection
in the service panel or a properly
driven and electrically grounded ground rod.
]
WARNING
Turn off electric power at fuse box before making any
line voltage connections. Follow local electrical codes.
I
INSTALL
YOUR THERMOSTAT
The thermostat
location has an important
effect on the
operation of your boiler system. BE SURE TO FOLLOW THE
INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT.
Locate the thermostat about five feet above the floor on an
inside wall. It may be mounted directly on the wall or on
a vertically mounted outlet box. It should be sensing average
room temperature, so avoid the following:
DEAD SPOTS:
Behind doors
Corners and alcoves
HOT SPOTS:
Concealed pipes
Fireplace
TV sets
Radios
Lamps
Direct sunlight
Kitchens
COLD SPOTS:
Concealed pipes or ducts
Stairwells - drafts
Doors - drafts
Unheated rooms on other side of wall
Set heat anticipator at 0.4 amps for boilers equipped with
standing pilot, and at 0.6 amps for boilers equipped
with
intermittent ignition. The 24 volt thermostat leads shall be
connected to the two wires tagged "24 volt thermostat" on
the boiler. For boilers with 67D-1 float type low water cut-
off, the two wires are black. One wire is located on the
secondary
of the 24 volt transformer, the second wire is
located on the pressure limit control. For boilers with PS-
802 probe type low water cut-off, one wire is green and
is located on terminal B of the PS-802, the second wire is
black and located on the pressure limit control.
ELECTRONIC
THERMOSTATS
Certain types of electronic therrnostats may lose their memory
or shut down. With 67D-!
float type low water cut offs,
this may occur each time the thermostat
calls for heat,
due to the internal circuit in the vent damper. With PS-802