Room Air Conditioner - Kenmore 253.70085 Use & Care Manual

Window type room air conditioner
Hide thumbs Also See for 253.70085:
Table of Contents

Advertisement

Available languages

Available languages

Room Air Conditioner
Troubleshooting
(Continued)
THE AIR CONDITIONER
RUNS TOO MUCH
Check
if...
Then...
Energy Saver is chosen.
Inside blower continues operating for one minute to use as much cooling that is
available in the evaporator.
Current Unit replaced an older unit.
Newer, higher efficiency Air Conditioner
may run longer to cool the room. Total
energy consumption
is less due to higher efficiency.
BTU size is too small.
A higher capacity unit may be required depending on the size of the room being
cooled. (Page 9)
WATER DRIPPING
FROM AIR CONDITIONER
- INSIDE ROOM
i Check if...
_:
Unit is not properly installed,
I Unit should be mounted on a 1/4" downward slope to the outside (1/2 bubble on a
Icarpenter's
level) to provide proper drainage, Reposition or shim cabinet as
necessary. DO NOT drill drain pan.
WATER DRIPPING
FROM AIR CONDITIONER
= OUTSIDE
ROOM
Check
if...
|_
/
Room is hot and humid.
I Normal operation during hot and humid days.
THE REMOTE WILL NOT OPERATE
AIR CONDITIONER
Check
if...
Then...
Batteries are not installed properly.
Verify batteries are installed properly. (Page 5)
Red light does not flash on the remote when the remote buttons
Verify batteries are installed properly, Install a new set of batteries,
are pressed,
The remote is pointed at the unit,
The remote may not work properly when used at extreme angles to the front of the
unit,
Guide
TYPICAL
AIR CONDITIONER
SOUNDS YOU MAY HEAR
Check
if...
Then...
High pitched whine or pulsating noise that cycles on and off.
Compressor - Normal noise due to modern high efficiency compressors.
(Page 12)
Rushing air sound.
FantMotor - Normal noise of higher efficiency fans pushing air further into the room.
(Page 12)
Pinging or swishing sounds.
Condenser - Normal noise of water hitting the condenser to increase energy
efficiency. (Page 12)
Gurgling or hissing sounds.
Evaporator - Normal noise of refrigerant passing through evaporation.
(Page 12)
Beeping.
Electronic Control - Normal noise when electronic control settings are changed.
Vibration.
Unit Vibration - Due to poor wall or window construction or incorrect installation.
(Page 12)
REMOTE SENSING
DEACTIVATING
PREMATURELY
(SOME MODELS).
Check
if...
Then...
Remote control not located within range.
Place remote control within 10 feet & 120 ° angle radius of the front of the unit.
Remote control signal obstructed.
Remove obstruction.
ROOM TOO COLD
Check
if...
IThen.
Set temperature too low.
I Increase set temperature.
m
Remote Sensing activated (on some models) and remote control
IRelocate
remote control or deactivate remote sensing.
located in Hot Spot
|
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

253.70135

Table of Contents