Power Line Transient
Maximum Peak Inrush and Crest Factor
Preparing for Installation
Heavy electrical loads from nearby machinery or equipment (elevators,
electric welders, etc.) can cause intermittent system errors, even if that that
equipemnt is on a separate circuit breaker. When faced with these
conditions, you should provide a separate, completely independent power
panel with an isolated ground and circuit panel coming directly from the
main building power source or secondary source. \\
The inrush current for the XP48 is 54 amps. The crest factor is 1.68.