Installation Of Rectangular Air Pipe - Sharp GB-X18JR Operation Manual

Split type room air conditioner
Table of Contents

Advertisement

Available languages

Available languages

Check of the indoor unit level
After the indoor unit is installed, be sure to check the level of the whole unit. The unit must be placed
horizontally, but the condensate pipe shall be installed obliquely, so as to facilitate the drainage of
condensate.
Condensate
Drainpipe

Installation of rectangular air pipe

Air Intake
Cautions:
• The air supply pipe, and the air intake pipe must be covered with a layer of thermal insulation, so as to avoid
thermal leakage and condensation. Firstly apply liquid nail on the pipes, then attach the thermal insulation
cotton with a layer of tinfoil. Use the liquid nail cover to fix it. Lastly use tinfoil adhesive tape to carefully seal
the joints; other good thermal insulation materials can also be used.
• The air supply pipes and the air intake pipes shall be fixed to the prefabricated boards of the ceiling by using
iron supports. The joints of the pipes must be sealed by glue so as to avoid leakage.
• The design and installation of air pipes must be in conformity with the relevant state engineering criteria.
• The edge of the air intake pipe must be at least 50mm away from the wall. The air intake must be covered
with filter.
• Silencing and shock absorption shall be considered in the design and installation of the air pipes. Additionally,
the noise source must be far away from where people stay. The air intake shall not be located above the
place where users stay (offices and rest places, etc.).
GREE_duct_eng_1022.indd 17
Level gauge
i
Air Intake
Enlarged View
Condensate Drainpipe
Air Intake
Ceiling Mount
E-7
Air Supply
As the inside of the unit is in the
negative pressure status, it is
required to set up a backwater elbow.
The requirements is:
A=B≥P/10+20(mm)
P is the absolute pressure inside the
unit. The unit of the pressure is Pa.
No. Name

Hanger
2
Air Intake Pipe
3
Air Supply
Canvas Air Pipe
4
Air Intake
5
Filter
6
Main Air Supply Pipe
Air Supply Outlet
7
Air Supply
08.10.27 3:32:11 PM

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gb-x24jrGb-x36jrGu-x18jrGu-x24jrGu-x36jr

Table of Contents