Minimum Clearance Tocombustible Materials; Installation - Regency F1100S Owners & Installation Manual

Freestanding woodstoves
Table of Contents

Advertisement

INSTALLATION

Please read the section below carefully as clearances depend on whether the airmate or the rear heat defl ector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.
Residential Installation "C" Vent (Single Wall)
Unit
Small F1100S
Large F3100L
Large S3100L
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove
collar to the ceiling level.
Unit
Small F1100S
Large F3100L
Large S3100L
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
Unit
Small F1100S
with Rear Defl ector
Large F3100L
with Rear Defl ector
Large S3100L Step Stove
8
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
A
with Airmate
13"
with Rear Defl ector
15"
with Airmate
18"
with Rear Defl ector
20"
Step Stove
18"
A
with Airmate
9"
with Rear Defl ector
13.5"
with Airmate
16"
with Rear Defl ector
20"
Step Stove
16"
A
with Airmate
11"
13"
with Airmate
18"
20"
18"
From Unit
From Corner
B
C
11"
8"
10.5"
11"
12"
8.5"
14"
10.5"
12"
8.5"
From Unit
From Corner
B
C
5"
3"
5"
5"
9.5"
8.5"
12"
8.5"
9.5"
8.5"
From Unit
From Corner
B
C
6"
6"
5"
9"
9.5"
10"
12"
10"
9.5"
10"
From Flue Center-line
D
E
F
25"
17.5"
20"
27"
17"
23"
32"
18.5"
22"
34"
20.5"
24"
32"
18.5"
22"
From Flue Center-line
D
E
F
21"
11.5"
15"
25.5"
11.5"
17"
30"
16"
22"
34"
18.5"
22"
30"
16"
22"
From Flue Center-line
D
E
F
23"
12.5"
18"
25"
11.5"
21"
32"
16"
23.5"
34"
18.5"
23.5"
32"
16"
23.5"
Regency Freestanding Woodstove

Advertisement

Table of Contents
loading

This manual is also suitable for:

F3100lS3100l

Table of Contents