SAFETY LABEL
This is a copy of the label that accompanies
each Regency Small Freestanding Woodstove
(F1100S).
LISTED SPACE HEATER, SOLID FUEL TYPE, ALSO
SUITABLE FOR MOBILE HOME INSTALLATION
MODEL: REGENCY SMALL FREESTANDING STOVE F1100S
TESTED TO: ULC S627 00 / UL 1482 1998 / UL 737 2000 REPORT NO.6621 (MAY 1993)
F1100S WITH
F1100S WITHOUT
AIRMATE SHIELD
AIRMATE SHIELD
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
F1100S WITH AIRMATE SHIELD
MEASURE
FROM
HEATER
RESIDENTIAL INSTALLATION USING
SINGLE WALL CONNECTOR
SIDEWALL
A 330 mm / 13 in
BACKWALL B 280 mm / 11 in
CORNER
C 205 mm / 8 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR MOBILE HOME
SIDEWALL
A 280 mm / 11 in
BACKWALL B 150 mm / 6 in
CORNER
C 150 mm / 6 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR RESIDENTIAL CLOSE CLEARANCE
SIDEWALL
A 230 mm / 9 in
BACKWALL B 125 mm / 5 in
CORNER
C 75
mm / 3 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR ALCOVE
SIDEWALL
G 280 mm / 11 in
BACKWALL H 180 mm / 7 in
MINIMUM ALCOVE CEILING HEIGHT: 2.15 M / 7 FT
MINIMUM CLEARANCES FOR HORIZONTAL CONNECTOR TO CEILING: 455 MM / 18"
THE SPACE BENEATH THE HEATER MUST NOT BE OBSTRUCTED. OPERATE ONLY WITH FIREBRICKS IN PLACE.
FOR USE WITH SOLID WOOD FUEL ONLY. USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION. DO NOT OBSTRUCT
COMBUSTION AIR OPENINGS. OPERATE ONLY WITH FIREBRICKS IN PLACE. OPERATE ONLY WITH DOOR CLOSED OPEN FEED DOOR TO FEED FIRE ONLY.
DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. DO NOT OVERFIRE IF HEATER OR CHIMNEY CONNECTOR GLOWS
YOU ARE OVERFIRING. INSPECT AND CLEAN CHIMNEY AND CONNECTOR FREQUENTLY. UNDER CERTAIN CONDITIONS OF USE CREOSOTE BUILDUP MAY
OCCUR RAPIDLY. KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL AWAY FROM HEATER. REPLACE GLASS ONLY WITH NEOCERAM GLASS.
COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON COMBUSTIBLE MATERIAL EXTENDING BENEATH THE HEATER AND TO THE FRONT AND SIDES AS
INDICATED OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL.
OPTIONAL COMPONENT: FAN, ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS, SCREEN DOOR
COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR
IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM:
SECURITY MODEL S2100, ICC EXCEL 2100 .
IN USA: LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA VENT
MODEL DVL, GSW SUPER PIPE 6, METAL FAB DOUBLE WALL. CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS SECURITY
MODEL S2100 OR MODEL ASHT, SELKIRK MODEL SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODEL SC OR METAL FAB TEMP/
GUARD, AMERI TEC HS, ICC EXCEL 2100 . USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION INSTRUCTIONS.
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY
4

SAFETY LABEL FOR F1100S

We have printed a copy of the contents here
for your review.
INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING
INSTRUCTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND
INSTALLATION INSPECTION IN YOUR AREA. USE 150 MM (6 IN.) DIAMETER MINIMUM 24 MSG BLACK
OR 25 MSG BLUED STEEL CONNECTOR WITH LISTED FACTORY BUILT CHIMNEY SUITABLE FOR USE WITH
SOLID FUELS OR MASONRY CHIMNEY.
SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED FOR
PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. DO NOT PASS CHIMNEY
CONNECTOR THROUGH COMBUSTIBLE WALL OR CEILING. DO NOT CONNECT THIS UNIT TO A CHIMNEY
FLUE SERVING ANOTHER APPLIANCE.
F1100S WITHOUT AIRMATE SHIELD
FLUE
MEASURE
FROM
CENTER LINE
RESIDENTIAL INSTALLATION USING
SINGLE WALL CONNECTOR
SIDEWALL
A 380 mm /15 in D 685 mm / 27 in
D 635 mm / 25 in
BACKWALL B 265 mm / 10.5in E 430 mm / 17 in
E 445 mm / 17.5in
CORNER
C 280 mm / 11 in F 585 mm / 23 in
F 510 mm / 20 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR MOBILE HOME
D 585 mm / 23 in
SIDEWALL
A 330 mm / 13 in
E 320 mm / 12.5in
BACKWALL B 125 mm / 5 in
F 460 mm / 18 in
CORNER
C 230 mm / 9 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR RESIDENTIAL CLOSE CLEARANCE
D 535 mm / 21 in
SIDEWALL
A 345 mm / 13.5in D 650 mm / 25.5in
E 290 mm / 11.5in
BACKWALL B 125 mm / 5
F 380 mm / 15 in
CORNER
C 125 mm / 5
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR ALCOVE
I 585 mm / 23 in
SIDEWALL
G 330 mm / 13 in
J 345 mm / 13.5in
BACKWALL H 125 mm / 5 in
MAXIMUM ALCOVE DEPTH 915 MM / 36 IN.
MANUFACTURED BY:
CAUTION
HOT WHILE IN OPERATION DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE
SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.
duplicate serial number
100
DO NOT REMOVE THIS LABEL
100
FLUE
HEATER
CENTER LINE
D 635 mm / 25 in
E 290 mm / 11.5in
F 535 mm / 21 in
in E 290 mm / 11.5in
in F 430 mm / 17 in
K 405 mm / 16 in
I 635 mm / 25 in
L
J 290 mm / 11.5in
M 150 mm / 6 in
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
6988 VENTURE ST.
DELTA, BC V4G 1H4
CERTIFIED TO COMPLY WITH JULY 1990,
PARTICULATE EMISSION STANDARDS.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
BACKWALL
B
E
A
D
BACKWALL
H
J
G
G
I
ADJACENT WALL
C
F
BACK
M
FLOOR
L
O
PROTECTION*
150 mm / 6 in
K
FRONT
* In Canada, floor protection must
extend 18" to the front and 8" to
each side of the stove.
MADE IN CANADA