Configuration

Set Configuration DIP Switches
Using a small tool, set the Configuration DIP Switches (located on the front panel of your unit, see diagram) to optimize Inverter/Charger
operation depending on your application. Warning: Make sure the unit is turned OFF before changing DIP Switch settings.
CONFIGURATION DIP SWITCHES
(SEE MANUAL OR TOP OF UNIT FOR INSTRUCTIONS)
1 2 3 4
5 6 7 8
1
Not Used
2
Select Line Connect Relay Transfer Time - OPTIONAL
Transfer Time
Switch Position
1/2 Cycle Transfer Time Up
1 Cycle Transfer Time
Down (factory setting)
3
Select Frequency - REQUIRED
Frequency
Switch Position
60 Hz
Up
50 Hz
Down (factory setting)
4
Select Line Voltage - REQUIRED
Voltage
Switch Position
208 VAC
Up
230 VAC
Down (factory setting)
5
Select Battery Charger Amp Setting
CAUTION: When switching to the High Charge Amp setting, the user
must ensure that the amp hour capacity of their battery system exceeds
the amperage of the High Charge Amp setting or the batteries may be
damaged or degraded.
6
Select Equalize Battery Charge - OPTIONAL
This DIP Switch is momentarily engaged to begin the process of
equalizing the charge state of your battery's cells by time-limited
overcharge of all cells. This can extend the useful life of certain types
of batteries; consult with your battery's manufacturer to determine if
your batteries could benefit from this process. The charge equalization
process is automatic; once started, it can only be stopped by removing
the input power.
7
8
9
Not Used
BATTERY
HIGH
MED
CONTROL
LOW
9 10 11 12
Faster
1
2
3
4
Slower
60 Hz
50 Hz
1
2
3
4
208 V
1
2
3
4
230 V
Low Charge Amp
1
5
6
7
8
High Charge Amp
5
6
7
8
OPERATION
LINE
INV
REMOTE
LOAD
Note: If you will use the Inverter/Charger to
support computers or other sensitive
electronic equipment loads, set the transfer
time to ½ cycle (switch #2 UP) to ensure
uninterrupted operation when the
Inverter/Charger transfers to battery power.
Battery Charger
Low Charge Amps (23A)
High Charge Amps (90A)
Setting Procedure
"Reset"
• Move to "Equalize" (DOWN) postition for three seconds.
• Move to "Reset" (UP) postition and leave it there. This is the factory default setting.
CAUTION: Do not leave DIP switch #3 in the down position after beginning process. Battery charge
equalization should only be performed in strict accordance with the battery manufacturer's instructions
and specifications.
"Equalize"
Battery Charge
Reset
Equalize
5
Switch Position
Up (factory setting)
Down
Switch Position
Up (factory setting)
Down (momentarily)