ProSys™ Softwired Switches, 1-, 2-, 4- and 8-button
RS4PS-x
DESCRIPTION
The ProSys Lighting Control System is a small network of
relay panels and occupant control switches linked by a 4-wire
dataline. Together, these devices form a reconfigurable
switching platform — one that uses "softwiring" instead of
hardwiring to link occupant switches to relays.
There are four basic configurations of SWS (or dataline
switches): the single-gang, 1-, 2- and 4-button RS1PS-x,
RS2PS-x and RS4PS-x, respectively, and the two-gang,
8-button RS8PS-x.
Each switch includes a bi-color LED status light for each control
button and a locator light. In addition, the 2-, 4- and 8-button
units have directories which accept standard
labels. The x suffix in the catalog number refers to button and
switchplate color: 2 = ivory, 4 = almond, 7 = white and 9 = grey.
ProSys softwired switches are available with a key-
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with
installation, operation or maintenance. Should further information be desired or should particular problems arise that are not covered for the purchaser's purposes,
the matter should be referred to the GE Company.
DEH40206 Installation Instructions
GE Total Lighting Control
ProSys Lighting Control System
Catalog Number RSxPS-x
enabled override function. The switch will be disabled
except when a key is used to activate a 5 minute
override period. Dip switch 4 must be in the off position
to enable this feature as shown on page 8. Order this
feature by adding a -K to the part number for the 1- 2-,
4-, and 8-button switch. For example: RS2PSxK.
Any button on a Softwire Switch may be softwired to:
• Any relay or group of relays within a single relay panel
• A channel within a single relay panel
• The same channel among multiple panels (requires an
RCLK8PS Softwired Clock, which also operates as a
handheld programmer)
3
" wide (9mm)
8
Before starting, read the following installation
instructions. If you have questions, call GE Total
Lighting Control Service at:
1-877-584-2685 (LTG-CNTL) in the USA and Canada.
RS1SWS-x
RS2SWS-x
RS8PS-x
1

Advertisement

loading

Summary of Contents for GE ProSys DEH40206

  • Page 1 These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise that are not covered for the purchaser's purposes, the matter should be referred to the GE Company.
  • Page 2 Note: To ensure good communications between panels, the installer must comply with the dataline specification. GE will not warrant a system using a dataline that does not meet our specification. To avoid questions, use GE RLONWIRE-4P (plenum rated). Do not run the dataline in conduit or wiring trays with power wires.
  • Page 3 DEH40206 Installation Instructions DATALINE SWITCH INSTALLATION AND TESTING Low-Resistance Red/Black Data Path The 1-, 2- and 4-button dataline switches mount in standard single-gang switch boxes. The 8-button unit mounts in a After wiring the last switch on the local dataline, disconnect standard 2-gang box.
  • Page 4 RELAY PANEL PANEL PANEL DATALINE PANELS 18/4 AWG NUMBERED 1500 FT. MAX. 02-01 02-02 SEQUENTIALLY GE RLONWIRE-4P BEGINNING AT 01 SWITCH 01-01 01-02 01-03 01-04 BUTTONS DATALINE SWITCHES FOR EACH PANEL (#1 AT TOP) NUMBERED SEQUENTIALLY (PANEL #-SWITCH #) MAXIMUM TOTAL NUMBER OF RELAY PANELS AND DATALINE SWITCHES IS 64...
  • Page 5 SOFTWIRING A DATALINE SWITCH TO A GROUP OF RELAYS Dataline switches are typically wired to a single relay or group of relays within a panel (See Figure 3, right). Wiring to Figure 3 – Softwiring a Dataline Switch a channel is a shortcut — it provides a simple way of With the wallplate removed and the switch’s master manually overriding all of the relays which are grouped to an button flipped open…...
  • Page 6 DEH40206 Installation Instructions SWITCH BUTTON LABELING The individual switch buttons provide space for ⁄ " wide x 1 ⁄ " long (9mm x 30mm) label directories. The directory labels can be attached simply by removing the clear lenses, positioning the labels and replacing the lenses as shown at right. If desired, the buttons may be completely removed from the base plate and labeled separately.
  • Page 7: Special Functions

    DEH40206 Installation Instructions SPECIAL FUNCTIONS ProSys is designed to provide flexibility without compromising simplicity in installation and operation. The Special Functions Figure 5 described here may be used to enhance the operation of your system, but they are not required in most installations. 01-01 Patterns 01-02...
  • Page 8 DEH40206 Installation Instructions SPECIAL FUNCTIONS (CONTINUED) Master Button Alternate Scenarios Figure 8 OFF/RESTORE — The Default Setting The Master Button on the 2-, 4- and 8-button switch is pre- configured to provide an OFF/Restore scenario. If several individual switch buttons are ON, hitting the Master turns all of those buttons OFF.
  • Page 9 2 on Cleaning Switch to turn on south cleaning area – lights in north cleaning area turn off, except for Zone 1. GE Total Lighting Control GE Total Lighting Control 41 Woodford Avenue, Plainville, CT 06062 ©2000 General Electric Company...