Technical Data

Nominal Chilling Capacity
Duty @ -15°C
Fans
Evaporating Temperature
HP Switch Setting
Refrigerant Control
Refrigerant
Refrigerant Quantity
System 1
System 2
Electrical Supply
Total Heat Rejection
Important Note
There are two refrigeration systems on this model
Refrigerant used is R404A.
The RBC20-60 has two separate refrigeration systems comprising, two condensing units, a twin circuit condenser (see
below) and a twin circuit evaporator. (See page 21for assembly details and page 22 for schematic dual circuit refrigeration
layout).
The condenser fan on system 2 is controlled by the HP switch, which is set at 18 BAR with a 3 BAR diff.
The RBC20-60R has the same refrigeration systems but the condensing units are remotely sited.
System 2
The parameter 'Capacity Enable' is set to 'AUTO' to allow for both condensing units to be running at the start of the chill
cycle therefore maximising the heat extraction from the product. On reaching 'HOLD' one of the condensing units will shut
down. During the 'HOLD' mode one compressor will control the temperature throughout unless the temperature exceeds
the capacity control limit.
Refrigerant control is by expansion valve to control the correct amount of refrigerant required to meet the demand of the
evaporator. (See page 21 for assembly detail).
Expansion Valve Setting (Superheat)
Adjust the superheat by turning the expansion valve setting spindle anti clockwise until back seated then turn the setting
spindle clockwise THREE FULL TURNS IN.
RBC20-60
60Kg
3800w
-15°C
TEV
R404a
1900grms
1900grms
400/3/50 – 16amp
1500w
CONDENSING UNIT ASSEMBLY RBC20-60
3
230/1/50 13 amp (Fans & Defrost)
20
RBC20-60R
60Kg
3800w
3
-15°C
TEV
R404a
HP Switch
System 1