Parameter Definitions

Pre-Chill
P01

Pre-Chill Enable

The air temperature, which the air probe must read before the condensing system is de-energised in the chill
mode of the Pre-Chill Program.
Range -15°C to 15°C.
P02
Chill Time
The period Pre-Chill is in the chill mode prior entering the Hold Mode.
Range 5 minutes to 60 minutes.
P03
Hold Temp
The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode
of the Pre-Chill program.
Range -15°C to 15°C.

Soft-Chill

P04
Air Temp
The temperature, which the air probe must read before the condensing system is de-energised in the chill mode
of the Soft-Chill Program.
Range -10°C to 15°C.
P05
Chill Time
The period Soft Chill program is in chill mode prior to entering Hold mode in a time based chill cycle.
Range 5 minutes to 480 minutes.
P06
Chill Temp
The temperature, which the Food Probe 1 must read before the condensing system is de-energised in the chill
mode of the Soft Chill program prior to entering the Hold mode of a temperature based cycle.
Range -5°C to 15°C.
P07
Hold Temp
The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode
of the Soft Chill program.
Range -5°C to 15°C.

Hard Chill

P08
Air Temp
The temperature, which the air probe must read before the condensing system is de-energised in the chill mode
of the Hard Chill Program.
Range -20°C to 15°C.
P09
Chill Time
The period Hard Chill program is in chill mode prior to entering Hold mode in a time based chill cycle.
Range 5 minutes to 480 minutes.
P10
Chill Temp
The temperature, which the Food Probe 1 must read before the condensing system is de-energised in the chill
mode of the Hard Chill program prior to entering the Hold mode of a temperature based cycle.
Range -15°C to 15°C.
P11
Hold Temp
The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode
of the Hard Chill program.
Range -15°C to 15°C.
P12
Change Time
The percentage period of a time based chill cycle, which is to have passed before automatically adjusting the air
temperature set point to 1°C.The range is adjustable in 5% increments.
Range 05% to 95%.
Alarm Buzzer
Function
Air Probe Offset
Coil Probe Offset
Food 1 Offset
Food 2 Enable
Function
Food 2 Offset
Food 3 Enable
Function
Food 3 Offset
Address
Integer
NO
YES
°K
-15
15
°K
-15
15
°K
-15
15
NO
YES
°K
-15
15
NO
YES
°K
-15
15
1
255
11
NO
0
0
0
NO
0
NO
0
255