Electrical Connections; Vdc Wiring; Accessories; Interlock Relay - Carrier HRVCCLHU Installation, Start-Up, And Operating Instructions Manual

Heat recovery ventilator sizes 1150, 1200, 1250, and 1330
Hide thumbs Also See for HRVCCLHU:
Table of Contents

Advertisement

WALL
CONTROL
Iooo ]
o
o
CONTROL
Fig. 12---Control Connections
A98410
All electrical connections
must comply with National
and Local
Electrical Codes, or other ordinances that might apply.
l'y_ [R'_lyi[0]_l
Do not use an extension cord as a power source for operating
the HRV.
Step 2--12-vdc
Wiring
The HRV circuit board, wall control, and accessories
operate on
12vdc. See Wall Control section, item Wiring and Fig. l I and 12
for more information.
ACCESSORIES
Step l_nterlock
Relay
The interlock
relay kit, Part No. KVAAC0101FIR
is required
when installing HRV into a forced-air heating and cooling system.
(See Fig. 13.) For additional
information,
refer to Installation
Iustructions supplied with interlock relay kit.
The purpose of interlock relay kit is to energize
indoor system
equipment (furnace or fan coil) blower whenever
HRV is calling.
If HRV is energized, and indoor system equipment is not, interlock
relay will energize and make R and G at indoor equipment. This
will insure fresh air distribution
throughout
the building via the
central duct system.
Step 2--20 Minute Timer
A push button timer can be used to override the wall control and
put the HRV into high speed for 20 minutes. Connect switches in
parallel and connect leads to HRV terminals 1, OC, and OL. (gee
Fig. 14.) Push button locations are ideal in special activity areas,
such as, bathrooms or kitchen, where high-speed exhaust operation
is needed for a short period of time.
NOTE: The 20 minute timer will not function properly
unless
HRV wall control is applied and working correctly.
Timing
function is internal to electronic circuit board, it is activated by a
momentary contact between OC and OL. The 1 connection
is to
illuminate the push button. The maximum number of push button
timers that can be applied is 5.
Step 3--60 Minute Adjustable Timer
A 60 minute adjustable timer can also be used to override wall
control and put HRV into high-speed operation for a select amount
of time. Connect timer in parallel with push button timers, or to
HRV terminals OC and OL. (See Fig. 14.)
The 60 minute timer will provide a minimum of 30 minutes, and
a maximum of 80 minutes of ventilation at high speed. When
adjustable timer expires, an additional 20 minutes will remain as a
result of the internal timer of HRV electronic circuit board.
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents