Flow Collars - Carrier HRVCCLHU Installation, Start-Up, And Operating Instructions Manual

Heat recovery ventilator sizes 1150, 1200, 1250, and 1330
Hide thumbs Also See for HRVCCLHU:
Table of Contents

Advertisement

collar
in stale-air
duct of HRV,
and record
airflow.
Next,
install
coil,u- in the fresh-air
duct and record airflow.
If 2 flow collars
are
available,
it will be much easier to read airflow
and properly
adjust
dampers
to balance
unit.
With speed control
at maximum
speed (high-speed
operation)
and
continuous
air exchange
occurring
with
outside,
connect
hoses
from
flow collar
to a magnehelic
gage. (See
Fig.
17.) The gage
must be leveled
and zeroed before use to read accurately.
If needle
falls below
zero, reverse
hose connections.
Measure
exhaust
air first, it is typically
the lowest
pressure
due to
nature
of system
and ductwork.
Next, measure
fresh air. If fresh air
reading
is higher than exhaust
reading,
adjust damper
until reading
is same.
If reading
is lower, return to exhaust
damper
and adjust to
obtain
same
reading.
You can use label on flow collar
to convert
static pressure
into airflow.
Once
HRV
is balanced
and dampers
are adjusted
to equalize
airflow,
use tape or drive screws
to prevent
damper
blades
from
moving.
Remove
flow collars
and secure
ducts. This
procedure
should
be repeated
to ensure
unit is balanced
properly.
A98400
Fig. 17--Magnehelic
Gage
NOTE:
The flow collar directional arrow !on flow collar1 must be
oriented in the airflow direction of unit.
NOTE:
Some field modification may be required to ensure proper
temporary
installation
of flow collar during
balancing
when
insulated flexible duct is used.
STALE AIR
TO OUTSIDE
6oc i-_-_
_._-_,/'
FRESH AIR
TO BUILDING
16°C
61°F
FRESH AIR
FROM OUTSIDE
0°C
32°F
>
STALE AIR
FROM BUILDING
22°C
72°F
A98403
Fig. 18---HRVCCLHU and HRVCCSVU
Cross Flow
STALE
AIR
TO OUTS_E
,=o.
FRESH
AIR
• .o..
FROM
OUTSIDE
STALE
AIR
b"""
FROM
BUILDING
FRESH
AIR
TO BUILDING
A99269
Fig. 20--HRVCCLHU
Airflow During
Air Exchange
STALE AIR _
TO OUTSIDE
2oc
36°F
FRESHAIR
TO BUILDING
20°C
68°F
FRESH AIR
FROM OUTSIDE
0oc
32°F
TALE AIR
EROMBUILDLNG
22oc
2OF
Fig. 19---HRVCCLVU
Counterflow
A98404
E
" ERE
TO BUILDING
Fig. 21 --HRVCCLHU
Airflow
During Defrost
STALE AIR
FROM
BUILDING
A99270
11