Carrier HRVCCLHU Installation, Start-Up, And Operating Instructions Manual page 17

Heat recovery ventilator sizes 1150, 1200, 1250, and 1330
Hide thumbs Also See for HRVCCLHU:
Table of Contents

Advertisement

Table 14---System Wiring
Colors
and
Connections
WALL CONTROL
WALL CONTROL
CONTROL
MODULE
WIRE
Terminal Block Identifi-
Color
Terminal NO.
Terminal Identification
Terminal
Block No.
cahon
J3-9
B
Black
J1-4
B
J3-8
G
Green
J1-3
G
J3-7
R
Red
J1-2
R
J3-6
y
Yellow
J 1-4
Y
Type
2--42ommunication
Problem
Or Unsupported
Mode
(Auto
MOdel unly_
All indicators
flashing at a rate of about once every 8 sec,
Communication
is not properly entered or is not working.
CASE 1
User
changes
the mode
on wall control
and HRV
responds
to
command
(OFF,
LOW,
or HIGH
speed).
Check
all wires to wall
control
particularly
red wire. (See Table
14-.)
CASE
2
User
changes
the mode
but, HRV
does
respond.
All indicators
flash
at a rate of about
once
every
8 sec. Check
all wires to wall
control
particularly
green
wire.
If problem
still exists,
test wall
control
with
5 ft of wire
from
HRV.
If this
works,
change
wall
control
module
inside
HRV.
RESET
To reset
HRV,
proceed
as follows:
l. Unplug
HRV from
115vac.
2. Wait
15 sec.
3. Plug HRV
into 115vac.
17