Figure 4
Communication cable connection
RMP_X1_J1
485-
4
3
485+
2
Shield
1
2.5
Mounting the RMP on Drywall
To hang the RMP on drywall or similar surface:
1. Drill four holes (6mm-by-26mm) in the wall, spacing them as shown in Figure 5.
2. Insert the four factory-supplied, plastic anchors into the holes.
3. Insert one screw into each anchor and tighten firmly.
4. Remove the four hooks from the RMP, reverse them, then reattach them to the RMP.
5. Hang the RMP on the wall by slipping the hooks over the heads of the screws and lowering the
RMP slowly until the screws are seated in the slotted portion of the hooks.
Figure 5
Mounting hole dimensions
Up to 328 ft. (100 m)
14-3/16"
(365mm)
Emerson
TM
Network P ower
S TATUS
F3
F1
F2
Liebert NX
Remote Monitor Panel
S ILE NCE ON/ OFF
F4
HELP
5
Installation
UPS_U2_J24
Shield
485+
485-
12"
(306mm)
1
2
3
4