Product Profile & Outline; Dimension - Delta Electronics RTU-EN01 Operation Manual

Modbus tcp remote i/o communication module
Table of Contents

Advertisement

Modbus TCP Remote I/O Communication Module RTU-EN01
Environment
Noise immunity
Operation
Storage
Shock/vibration
immunity
Certificates
Electrical specification
Power supply voltage
Power fuse capacity
Power consumption
Insulation voltage
Weight
2
Product Profile & Outline

2.1 Dimension

4
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV,
Communication I/O: ±2KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz,
10V/m
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150kHz ~ 80MHz,
3V/m
Surge Test (Biwave IEC61132-2, IEC61000-4-5): Power line 0.5KV DM, Ethernet
0.5KV CM, RS-485 0.5KV CM
0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
-25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC
68-2-27 (TEST Ea)
24VDC (-15% ~ 20%) (with DC input polarity reverse protection)
1.85A/30VDC, Polyswitch
2W
500VDC
116g
37.4
LAN
POWER
RUN
RUN
BAT.LOW
STOP
Unit: mm