1

Introduction

To ensure correct installation and operation of RTU-EN01, please read this manual carefully before using your
RTU-EN01. RTU-EN01is an Ethernet remote I/O module for remote setting through Delta's DCISoft. RTU-EN01
supports maximum 256 digital input/output points. RTU-EN01 supports Modbus TCP protocol and can be used
for remote monitoring with graphic control software or human machine interface. RTU-EN01 can also be used as
a Modbus TCP gateway, supporting the conversion from Modbus TCP commands to Modbus ASCII/RTU. In
addition, in MDI/MDI-X auto-detect, jump wire is not needed when you choose the network cable.

1.1 Features

Supporting smart PLC functions, counter, timer and real-time clock. Able to operate independently without
control of PLC main processing unit or programming.
Able to auto-detect 10/100 Mbps transmission speed; MDI/MDI-X auto-detect.
Supporting maximum 16 digital input/output modules (Max. 256 I/O points) and 8 analog input/output
modules.
Supporting maximum 16 sets of Modbus TCP connections.
Supporting Modbus TCP/Modbus gateway (supporting Master mode, connectable to maximum 32 devices).
Parameters can be set up on webpage.

1.2 Specifications

Ethernet interface
Interface
Transmission method
Transmission cable
Transmission speed
Communication protocol
Serial communication interface (COM1)
Interface
Transmission method
Communication speed
Communication format
Communication protocol
Transmission cable
Serial communication interface (COM2)
Interface
Transmission method
Transmission distance
Communication speed
Communication format
Communication protocol
DVP-PLC Operation Manual
RJ-45 with Auto MDI/MDIX
802.3, 802.3u
Category 5e, 100m (Max)
10/100 Mbps Auto-Detection
ICMP, IP, TCP, UDP, DHCP, NTP, Modbus TCP, HTTP
Mini Dim
RS-232
19,200 bps
Stop bit: 1; Parity bit: None; Data bit: 8
Delta Configuration
DVPACAB215 / DVPACAB230 / DVPACAB2A30
3 PIN feed-through terminal
RS-485
1,200m
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200
bps
Stop bit: 1, 2; Parity bit: None, Odd, Even; Data bit: 7, 8
Modbus ASCII、Modbus RTU
3