Modbus TCP Remote I/O Communication Module RTU-EN01
5.3 Device Type & Device Address
Device type
RX
RY
T
R
C
Device type
BR
T
C
RCR
6

Setting up Software

This section gives instructions on how to set up RTU-EN01 by DCISoft and explanations on each setup page.
RTU-EN01 is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall.
See the explanations below on the software.
6.1 Setting up Communications & Searching for Communication Modules in DCISoft
Broadcast search
1.
Open DCISoft on the PC and click on the "IP Search" icon.
16
Modbus address (Hex)
0x0400 ~ 0x04FF
0x0500 ~ 0x05FF
0x1600 ~ 0x160F
0x1900 ~ 0x190F
0x1E00 ~ 0x1E0F
Modbus address (Hex)
0x0000~0x0040
0x1600~0x160F
0x1E00~0x1E0F
0x3000~0x3190
Discrete input
6-digit Modbus address (Dec)
101025 ~ 101280
Coil
001281 ~ 001537
005633 ~ 005649
006401 ~ 006416
007681 ~ 007696
Holding register
6-digit Modbus address (Dec)
400001~400064
405633~405649
407681~407696
412289~412689
Number
256
256
16
16
16
Number
64
16
16
400
DVP-PLC Operation Manual