Delta Electronics RTU-EN01 Operation Manual page 13

Modbus tcp remote i/o communication module
Table of Contents

Advertisement

Modbus TCP Remote I/O Communication Module RTU-EN01
Code
F0
Returning to default setting
F1
RTU-EN01 being powered
F2
Power supply in low voltage
F3
Internal error. Manufacturing error.
F5
Network connection error
F6
Insufficient TCP connection
F7
RS-485 setting error
F8
IP setting error
F9
Right-side module error
04
Slave error
0b
No response from station
B R # 11: C om m u n icat io n Tim e- ou t ( ms)
Explanations:
For setting up the communication time-out. Default = 5,000ms. For example, if you wish to set up the
communication time-out to 7 seconds manually, write 7000 to BR#11. Range: 5 ~ 65,535.
BR# 12: C ommu n icat io n De la y Time ( ms)
Explanations:
For setting up the minimum interval time between every Modbus command. Default = 0ms. For example, if you
wish to set up the communication delay time to 100ms manually, write 100 into BR#12. Range: 0 ~ 65,535.
BR# 13: TCP Co nn ectio n Id le Time ( s)
Explanations:
For setting up the TCP connection idle time. Default = 30 seconds. For example, if you wish to set up the idle time
to 7 seconds manually, write 7 into BR#13. Range: 5 ~ 65,535.
B R # 23: N um b er of A n a lo g I /O M od u le s
Explanations:
Read the number of right-side modules from BR#23. Max. 8.
BR# 24 ~ #3 1: ID of th e 1
Explanations:
Read the ID of the 1
DVP-PLC Operation Manual
Indication
s t
t h
~ 8
A n a lo g I /O Mo du le
st
th
~ 8
analog I/O modules from BR#24 ~ BR#31.
--
--
Check if the power supply of the module works normally.
1. Check if the settings of smart PLC are incorrect.
2. Re-power RTU-EN01. If the error still exists, try step 3.
3. Reset RTU-EN01. If the error still exists, send the module back to
the manufacturer for repair.
Check if RTU-EN01 is connected normally to the network.
Check if the number of connected modules exceeds the maximum.
Check if the RS-485 communication format is correct.
1. DHCP request failure.
2. IP setting error.
3. MASK setting error.
4. Gateway does not exist in the same subnet.
5. Returning to default setting.
Check if the configuration of the right-side module has been modified. If
the error still exists, check if the number of I/O points exceeds the
maximum and whether the there are more than 8 analog I/O modules
connected.
1. Check if RTU-EN01 and RS-485 is connected normally.
2. Check if the series transmission speed is consistent with that of other
nodes on the network.
How to correct
11