Modbus TCP Remote I/O Communication Module RTU-EN01
BR#
Attribute
ID of the 1st analog
24
R
I/O module
ID of the 2nd analog
25
R
I/O module
ID of the 3rd analog
26
R
I/O module
ID of the 4th analog
27
R
I/O module
ID of the 5th analog
28
R
I/O module
ID of the 6th analog
29
R
I/O module
ID of the 7th analog
30
R
I/O module
ID of the 8th analog
31
R
I/O module
32 ~ 49
Reserved
50
R/W
RTC settings
51
R/W
Year
52
R/W
Week
53
R/W
Month
54
R/W
Day
55
R/W
Hour
56
R/W
Minute
57
R/W
Second
58 ~ 59
Reserved
60
Reserved
61 ~ 63
Reserved
Symbol "R" refers to ready only; "R/W" refers to read and write.

4.2 Explanations on BR

BR#0: Model N a me
Explanations:
1. Model code of RTU-EN01 = H'0600.
2. You can read the model code in the program to see if the extension module exists.
BR# 1: F irmw are Ve rs ion
Explanations:
The firmware version of RTU-EN01 is displayed in hex, e.g. H'0100 indicates version V1.00
BR# 2: Re le ase D ate o f th e Vers ion
Explanations:
Displaying the data in decimal form. 10,000s digit and 1,000s digit are for "month"; 100s digit and 10s digit are for
"day". For 1s digit: 0 = morning; 1 = afternoon.
Example: 12191 indicates the version released in the afternoon of December 19.
DVP-PLC Operation Manual
Content
ID of the 1st analog I/O module
ID of the 2nd analog I/O module
ID of the 3rd analog I/O module
ID of the 4th analog I/O module
ID of the 5th analog I/O module
ID of the 6th analog I/O module
ID of the 7th analog I/O module
ID of the 8th analog I/O module
Settings of the real-time clock
Range: 1970 ~ 2099
Range: 1 ~ 7
Range: 1 ~ 12
Range: 1 ~ 31
Range: 0 ~ 23
Range: 0 ~ 59
Range: 0 ~ 59