Mitsubishi Electric MN converter Operating Manual page 97

Electric air-conditioner network system
Hide thumbs Also See for MN converter:
Table of Contents

Advertisement

3.13.4.1 Starting the interlock control settings on DIDO Controllers
The password is needed to make the settings for interlock control. Only the allowed administrator can perform
the settings. To make the settings, enter the password first to be identified as an administrator. The
procedures are shown below. The setting procedures are the same for AI Controllers.
(1) Click [Option] in the menu bar and
select [DIDO/AI/PI] -> [Interlock control option] in
the sub-menu.
(2) Interlock control option screen will appear.
(3) Click the checkbox of [I agree] to accept the agreement.
Caution:
Read the agreement carefully.
(4) Enter the password.
(5) Click [OK].
(6) "Do you want to enable the DIDO/AI interlock setting?"
will appear, click [Yes].
(7) "DIDO/AI interlock setting has been enabled."will appear,
click [OK].
(8) [DIDO/AI interlock setting ] in [DIDO/AI/PI] sub-menu
becomes active, and the settings can be made.
NOTE:
[DIDO/AI interlock setting] will be kept active once it becomes active.
To make it inactive, enter the password to make a inactivation on the interlock control option screen
[ Refer to 3.13.4.1 (4) ].
96