Operation Monitor Mail Communication Mode Trouble
Trouble
Operation monitor mail cannot receive
normally.
The analysis screen of the operation
monitor data (which carried out mail
acquisition by OFFLINE) is not displayed.
Cause
A mail address and SMTP server
information were made a mistake in and
set up by mail communication setup.
The mail address a contract of is not
made with a provider was set as [FROM:
Mail Address].
(When using dialup)
The mail address of recipient (To:) is not
an address only for Maintenance Tools.
(The mail address used usually is set up.
In this case, once other mail software
receives mail, operation data mail will be
deleted from a mail server.)
The system configuration information
acquired from G-50A immediately after a
mail communication setup was not
acquired normally.
Mail communication mode was set up
from the Maintenance Tool of a remote
place, and the mail address of recipient
(To:) was set as another addressing to a
Maintenance Tool of a remote place.
(System configuration information mail is
transmitted from G-50A immediately after
a mail communication setup.
However, the Maintenance Tool by the
side of a setup is using dial-up service,
and mail transmission cannot be
performed.
Consequently, since the Maintenance Tool
with which mail is transmitted cannot
acquire system configuration information
mail, even if it receives after that operation
monitor data mail, it does not indicate by
normal.
139
Repair
Please set up the right information again
after performing "Stop mail
communication" of 3.4 (2).
Please set the regular mail address a
contract of is made with the provider to
[FROM: Mail Address].
The mail address of recipient (To:)
acquires and sets up the address only for
Maintenance Tools.
Please delete the corresponding data.
Text conversion can be carried out and
data can be outputted.
When mail communication mode is set up
from the Maintenance Tool of a remote
place, mail acquisition of operation data
can be performed only with the
Maintenance Tool which set up.
Please make a set the mail address of a
Maintenance Tool which set mail
communication mode to the mail address
of recipient (To:).