Energy Management/Front Desk Control - Carrier PREMIER 52P SERIES Architects And Engineers' Manual

Architects and engineers’ manual packaged terminal air conditioners and heat pumps
Hide thumbs Also See for PREMIER 52P SERIES:
Table of Contents

Advertisement

ROOM 100
B
W
PTAC #1
LEGEND
AWG — American Wire Gage
B
— Black
PTAC — Packaged Terminal Air Conditioner
W
— White
NOTES:
1. To size transformer, use the following equation:
Quantity of PTAC units x 12 va = Transformer Size (va)
Example: 110 PTAC Units x 12 va = 1320 va Transformer
2. Following are recommended wire sizes:
AWG WIRE SIZE NO.
24
22
20
18
16
FRONT DESK SWITCH PANEL
ROOM 101
B
W
PTAC #2
MAXIMUM LENGTH (ft)
400
600
900
1500
2000
Typical Wiring Schematic for Energy Management Kit
ROOM N
B
PTAC #N
49
FIELD-SUPPLIED
24-V
TRANSFORMER
(SEE NOTE 1)
W

Hide quick links: